UT-1102

SIGNAL ISOLATOR

2.3       Technical Specifications

High scale / Low scale

Full range  as per input selection

Power Supply

Operating Ambient

Temp. : 0~50˚C, Humidity : Below 90% Non condensing

Input

Type Of Input

T/C

K, J, R, S, T, E

RTD

Pt-100, Pt-1000, Cu-53 [2 wire, 3 wire]

Linear : 4 ~20mA DC, 0~20mA DC, 0 ~5 Amp AC

CURRENT [Analog]

VOLTAGE [Analog]

Linear : 0.5~2.5VDC, 1~5VDC, 0~10VDC

SPECIAL ON DEMAND

Linear : 0~75m/0~200mVDC, 0~100/200/300VDC

Accuracy

T/C

+ 0.25% of Full Scale

RTD

Class A

+ 0.1% of Full Scale

ANALOG [V & I]

SPECIAL ON DEMAND

+ 0.1% of Full Scale

Automatic Software based self compensation

Cold Junction Comp.

1 ms to 200 ms default 200 ms.

Response time

>330 K for Voltage ,mV, and T/C,  100 R for current

Input Impedance

Prog. parameters

Baud rate, Parity, Node address, Stop bit

Max. Connections

Communication

Up to 128 Units

Programmable

Parameters

Display resolution

Setpoint / Hysteresis

Relay logic

Full range  as per input selection

-1999 to 9999 fully configurable for linear input

F.S. high & low alarm

TECHNICAL SPECIFICATIONS

Transmitter Power Supply

10/12/24VDC @ 30mA max, Isolated

Isolation

1.5 KV AC Between

Input to output , Input to power, output to power

output to output (in case of multipul output )

Output

Output Type

Nos off Output

0-20mA, 4-20mA, 0-10V, 0-2V, 0-5V, 0-10VDC

1/2/3/4 all are isolated.

Other

Dimensions & Mounting

110/230

or

10

VAC, 50/60 Hz

24 VDC

watts maximum

As per order & Din rail mounted

K

: -50~1200˚C

R

: 0~1750˚C

T

: 0~400˚C

INPUT

RANGE

RTD

Pt-100 : -50~400˚C

Linear All DC & AC : -1999~9999 Display

CURRENT [Analog]

VOLTAGE [Analog]

Linear All DC : -1999~9999 Display

SPECIAL ON DEMAND

Linear : -1999~9999 Display

T/C

INPUT RANGE

J

: -50~750˚C,

S

: 0~1750˚C,

E

: -50~400˚C,