Mate-N-Lock plug, a poor connection between the
UCB and economizer Mate-N-Lock plugs, loose
wiring from the Mate-N-Lock plug to the econo-
mizer, back to the Mate-N-Lock plug, and from the
Mate-N-Lock plug to the Y1 “ECON” terminal. The
economizer board may have faulted and is not
returning the 24 volts to the Y1 “ECON” terminal
even though the economizer is not providing free
cooling. To test the economizer board, disconnect
the Mate-N-Locks and jumper between the WHITE
and YELLOW wires of the UCB’s Mate-N-Lock
plug.
13. The UCB can be programmed to lock out compres-
sor operation during free cooling and in low ambi-
ent conditions. These options are not enabled by
default. They can be checked by local distributors.
14. If none of the above corrected the error, test the
integrity of the UCB. Disconnect the C1 terminal
wire and jumper it to the Y1 terminal. DO NOT
jump the Y1 to C1 terminals. If the compressor
engages, the UCB has faulted.
15. If none of the above correct the error, replace the
UCB.
GAS HEAT TROUBLESHOOTING GUIDE
NOTE:
To find the Btu input, multiply the number of
cubic feet of gas consumed per hour by the
Btu content of the gas in your particular locality
(contact your gas company for this information
- it varies widely from city to city.).
On calls for heating, the draft motor operates and the
furnace lights but the supply air blower motor does not
energize after a short delay (the room thermostat fan
switch is in “AUTO” position).
1.
Place the thermostat fan switch in the “ON” posi-
tion. If the supply air blower motor energizes, go to
Step 9.
2.
If the supply air blower motor does not energize
when the fan switch is set to “ON,” check that line
voltage is being supplied to the contacts of the M3
contactor, and that the contactor is pulled in. Check
for loose wiring between the contactor and the sup-
ply air blower motor.
Troubleshooting of components may require
opening the electrical control box with the
power connected to the unit.
Use extreme
care when working with live circuits!
Check
the unit nameplate for the correct line voltage
and set the voltmeter to the correct range
before making any connections with line termi-
nals.
When not necessary, shut off all electric power
to the unit prior to any of the following mainte-
nance procedures so as to prevent personal
injury.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause
improper and dangerous operation, which
could cause injury to person and/or damage
unit components. Verify proper operation after
servicing.
The furnace may shut down on a high tem-
perature condition during the procedure. If
this occurs, the UCB energize the supply air
blower motor until the high temperature limit
has reset. Caution should be used at all
times as the supply air blower may energize
regardless of the room thermostat fan switch
position.