FIGURE 25 - DJ060 OPERATING PRESSURES
GAS HEAT TROUBLESHOOTING GUIDE
Before beginning symptomatic troubleshooting activi-
ties read the flash code LEDs on the unit control board
(UCB) and the ignition control board (ICB). Fault codes
have a quick sequence of flashes indicating the flash
code number followed by a pause with the LED off. The
ICB flash codes are repeated until the fault is cleared.
The ICB monitors itself, the centrifugal switch, lockout
due to > 16 pilot flame losses, primary limit, rollout and
a flame present when the ICB expects no flame.
With power applied to the unit, if the LED on the ICB is
flashing the heartbeat and the furnace will not operate,
then proceed to the symptomatic troubleshooting sec-
tion. If the ICB LED is not flashing, then perform the ICB
troubleshooting procedures. If the ICB has a flash code
other than the heartbeat, then determine the flash code
and locate its troubleshooting procedures in the flash
150
170
190
210
230
250
270
290
310
330
65
70
75
80
85
90
95
100
Suction Pressure (psig)
Discharge Pressure (psig)
65°F Outdoor
105°F Outdoor
95°F Outdoor
85°F Outdoor
75°F Outdoor
115°F Outdoor
Troubleshooting of components may require
opening the electrical control box with the power
connected to the unit.
Use extreme care when
working with live circuits!
Check the unit
nameplate for the correct line voltage and set
the voltmeter to the correct range before making
any connections with line terminals.
When not necessary, shut off all electric power
to the unit prior to any of the following mainte-
nance procedures so as to prevent personal
injury.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause
improper and dangerous operation, which
could cause injury to person and/or damage
unit components. Verify proper operation after
servicing.
The furnace may shut down on a high temper-
ature condition during the procedure. If this
occurs, the UCB energize the supply air blower
motor until the high temperature limit has
reset. Caution should be used at all times as
the supply air blower may energize regardless
of the room thermostat fan switch position.