66399-YIM-C-0405
48
Unitary Products Group
TABLE 36: ELECTRICAL DATA - DF072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
NONE 0.0
0.0
40.8
50
2CE04510525
2
4.0
11.1
40.8
50
2CE04510725
2
5.6
15.5
40.8
50
2CE04511025
8.0
22.2
46.6
50
2CE04511525
11.9
33.0
60.4
70
2CE04512025
15.9
44.1
74.2
80
2CE04513025
22.2
61.6
96.1
100
NONE 0.0
0.0
40.8
50
2CE04510525
2
5.3
12.7
40.8
50
2CE04510725
2
7.5
18.0
41.6
50
2CE04511025
10.6
25.5
50.9
60
2CE04511525
15.9
38.2
66.8
70
2CE04512025
21.2
51.0
82.7
90
2CE04513025
29.6
71.2
108.0
110
NONE 0.0
0.0
20.2
25
2CE04510746
2
6.8
8.2
20.2
25
2CE04511046
2
10.1
12.1
24.7
25
2CE04511546
2
13.6
16.4
29.9
30
2CE04512046
2
19.5
23.5
38.8
40
2CE04513046
2
28.8
34.6
52.8
60
NONE 0.0
0.0
16.6
20
2CE04511058
10.6
10.2
20.2
25
2CE04511558
15.9
15.3
26.6
30
2CE04512058
21.2
20.4
33.0
35
2CE04513058
30.4
29.3
44.1
45
2.3
156
1.3
2.6
573-3-60
7.4
54
1.3
460-3-60
ID Blower
Motor
FLA
OD Fan
Motors
FLA
RLA
Each
LRA
Each
Max Fuse /
BRKR
1
Size
Amps
Heater
kW
Electric Heater
Model No.
3
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Conv
Outlet
Amps
75
230-3-60
Model
Tonnage
Voltage
Compressors
18.6
156
10.0
5.0
6
4.0
208-3-60
18.6
2.0
5.2
5.2
9.0
2.3
10.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.