257098-BTG-A-0506
Unitary Products Group
39
pressor operation is also possible. Dampers shall fully
close on power loss.
•
MOTORIZED OUTDOOR AIR DAMPERS
- Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB
- 14" and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
BAROMETRIC RELIEF DAMPER
- Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•
POWER EXHAUST OPTION
- To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD
-
Contains all hood panels and the hardware for assem-
bling.
•
MANUAL OUTDOOR AIR DAMPER
•
COIL GUARD KIT
- Guard for condenser coil.
•
HAIL GUARD