Page
7
Installation Manual 802
SunFrame™ Code-Compliant Planning and Assembly
Kyocera KC120 / KC125G
24" rafter (foot) spacing 34
187 281 374 468
32" rafter (foot) spacing 45
249 374 499 623
48" rafter (foot) spacing 68
374 561 748 NA*
Kyocera KC158G / KC167G
24" rafter (foot) spacing 28
169 254 339 423
32" rafter (foot) spacing 37
226
339 452 564
48" rafter (foot) spacing 56
339 508 677 847
Photowatt PW1250
24" rafter (foot) spacing 30
163 245 327 408
32" rafter (foot) spacing 39
218 327 436 544
48" rafter (foot) spacing 59
327 490 653 817
Photowatt PW1650
24" rafter (foot) spacing 31
162 244 325 406
32" rafter (foot) spacing 41
216 325 433 541
48" rafter (foot) spacing 62
325 487 649 812
Sharp 70, 140
24" rafter (foot) spacing 26
153 229 306 382
32" rafter (foot) spacing 34
204 306 408 510
48" rafter (foot) spacing 52
306 459 612 765
Sharp 165, 175, 185
24" rafter (foot) spacing 35
207 310 413 517
32" rafter (foot) spacing 47
276 413 551 689
48" rafter (foot) spacing 70
413 620 827 NA*
Sharp 167
24" rafter (foot) spacing 28
174 261 349 436
32" rafter (foot) spacing 37
232 249 465 581
48" rafter (foot) spacing 55
349 523 697 871
Shell SQ140, SQ150, SQ160
24" rafter (foot) spacing 32
213 319 425 531
32" rafter (foot) spacing 43
283 425 567 708
48" rafter (foot) spacing 64
425 638 850 NA*
To meet code, your design point loads (capacity per footing) must be at
or above those indicated. The installer is solely responsible for verifying
that the roof can withstand these design point loads. For specifi cations
based on design wind pressure values greater than 50 pounts per square
Minimum design live load
Minimum as a function of
design design wind pressure
dead
load 20 psf 30 psf
40 psf
50 psf
ASE 300
24" rafter (foot) spacing 58
248 373 497 621
32" rafter (foot) spacing 77
331 497 662 828
48" rafter (foot) spacing 116
497 745 NA* NA*
AstroPower APi100, APi110
24" rafter (foot) spacing 33
194 291 387 484
32" rafter (foot) spacing 44
258 387 516 646
48" rafter (foot) spacing 66
387 581 775 NA*
AstroPower APi165, APi173
24" rafter (foot) spacing 34
194 291 388 485
32" rafter (foot) spacing 46
258 388 517 646
48" rafter (foot) spacing 69
388 582 775 NA*
BP Solar 3160, 4160, 5170, SX150
24" rafter (foot) spacing 33
208 313 417 521
32" rafter (foot) spacing 44
278 417 556 694
48" rafter (foot) spacing 67
417 625 833 NA*
Evergreen EC94, EC102, EC110
24" rafter (foot) spacing 35
208 312 416 520
32" rafter (foot) spacing 46
277 416 555 693
48" rafter (foot) spacing 69
416 624 832 NA*
Minimum design live load
Minimum as a function of
design design wind pressure
dead
load 20 psf 30 psf
40 psf
50 psf
Table 2. SunFrame™ Loads (pounds per footing) at Standard Rafter Spacings
foot, contact UniRac. In general, the minimum design live load equals the
footing spacing times the rail spacing times the design wind presure from
Table 1.
*NA = not applicable. Never allow total load (live load plus dead load) to
exceed 1,000 pounds per footing.
Table 3. Lag Screw Design Pull-Out Values
(pounds per embedded 1" thread depth)
in Typical Roof Truss Lumber
Specifi c
Lag screw
gravity
5/16"
3/8"
Douglas Fir — Larch
0.50
266
304
Douglas Fir — South
0.46
235
269
Engelmann Spruce, Lodgepole
Pine (MSR 1650 f & higher)
0.46
235
269
Hem — Fir
0.43
212
243
Hem — Fir (North)
0.46
235
269
Southern Pine
0.55
307
352
Spruce, Pine, Fir
0.42
205
235
Spruce, Pine, Fir
(E of 2 million psi and higher
grades of MSR and MEL)
0.50
266
304
Sources:
UBC 1997, American Wood Council.
Notes: (1) Thread must be embedded in a rafter or other structural roof
member. (2) Pull-out values incorporate a 1.6 safety factor recommended
by the American Wood Council. (3) See UBC for required edge distances.
Thread
depth
*NA = not applicable. Never allow total load (live load plus dead load) to
exceed 1,000 pounds per footing.