8

installation and operation manual

 

Temporary mode:

This mode is automatically set when the pump, for a variety 

of reasons, cannot produce Pmax. In this case the pump is 

switched off with 30-second delay when water flow stops and 

rate thereof drops to 2 l/min. The pump is switched on when 

water flow appears (more than 2 l/min) but not earlier than in 

2 seconds after the pup switching off.

3.  In the absence of water flow and the system pressure 

drop to Рmin, the pump is switched on and operates during 

30 seconds. If after thirty-second interval water flow rate 

is not more than 2 l/min, the control unit is transferred to 

pre-emergency mode.

4. After transfer to pre-emergency mode, the device produces 

6 automatic trial starts of 30 seconds each – in 5, 20 and 

60 minutes and then – in 6, 12 and 24 hours. When water 

appears during any trial starts, the pump is automatically 

switched on and transferred to pump mode.

5. In the absence of water during full cycle of trial starts, the 

pump is switched off and transferred to emergency mode.

6. Exit from emergency mode is made manually by discon-

necting the control unit from power line for not less than 6 

seconds.

ATTENTION!

 

The control unit can enter emergency mode not 

only in the absence of water flow but also when supply voltage 

drops below 170 V, in case of improper installation, impeller 

jamming and in other emergency situations. Before restarting 

the device, make sure that the cause of accident is eliminated. It 

is not permissible to use the pump at very low water flow - less 

than 2 l/min.

Summary of Contents for TURBI-M2

Page 1: ...Installation and Operation Manual PUMP AUTOMATIC CONTROL UNIT TURBI M2 Manual EN ...

Page 2: ......

Page 3: ... vibration pumps with power of up to 1 5 kW according to flow and minimum pressure Pmin it can be also used as the pump protection device against dry running and other emergency situations The device maintains thresholds of Pmax and Pmin set by pressure sensor in water supply system switches the pump on at Pmin and switches the pump off at Pmax In case the pump for some reason does not produce the...

Page 4: ...rol unit as a set 1 Wire nut СИЗ 2 for grounding wires un der upper cover of the device 1 Installation and Operation Manual 1 Package 1 DESCRIPTION AND OPERATING PRINCIPLE TURBI M2 control unit consists of sealed plastic housing 1 and upper cover with rubber bushing 2 On the housing ...

Page 5: ...bine vanes receives pulses and delivers them to microcontroller The microcontroller processes this information and power relay turns the pump on At this time the pump continuously delivers water producing the system pressure corresponding to pressure thresholds Pmin cut in pressure and Pmax cut off pressure preset by sensor If the pump for some reason cannot produce the system pressure Рmax then i...

Page 6: ...r sensibility 2 l min 6 Pump cut in pressure Рmin 1 5 1 8 bar 7 Max permissible water flow 100 l min 8 Pressure thresholds Pmin and Pmax are determined accor ing to types of pressure sensor Pmin Pmax bar Threshold range bar Type 1 1 5 3 0 0 3 Type 2 2 0 3 5 Type 3 2 5 4 0 Type 4 3 0 4 5 9 Permissible range of water temperature 5 35 С at ambient temperature from 1 to 40 С 10 Requirements to pumped ...

Page 7: ...isconnect the device from power line and open valves in order to blow the system pressure down 3 Do not use the control unit without grounding 4 Do not use the control unit with upper cover removed 5 The device dismounting and repair shall be performed only by maintenance specialists OPERATION ALGORITHM 1 At water flow rate of more than 2 l min the pump is switched on and starts to pump water cont...

Page 8: ...ergency mode the device produces 6 automatic trial starts of 30 seconds each in 5 20 and 60 minutes and then in 6 12 and 24 hours When water appears during any trial starts the pump is automatically switched on and transferred to pump mode 5 In the absence of water during full cycle of trial starts the pump is switched off and transferred to emergency mode 6 Exit from emergency mode is made manual...

Page 9: ...ntermittently flashes out one time a second Emergency mode the pump is switched off LED lights continuously HYDRAULIC CONNECTION Install the suction line in accordance with Surface and Sub mersible Pumps Operation Manual TURBI M2 control unit shall be installed on the pump dis charge line All connections must be sealed When installing the device do not use excessive force in avoidance of disrup ti...

Page 10: ...TS FOR INSTALLATION OF TURBI M2 CONTROL UNIT ON SUR FACE PUMP OUTLET ATTENTION It is not permissible to install the unit vertically on surface pump outlet without check valve VARIANTS FOR INSTALLATION OF TURBI M2 CONTROL UNIT WHEN USING IT FOR ON OFF PUMP AUTO MATIC CONTROL ATTENTION The required condition for TURBI M2 control unit operation in automatic mode is the presence of pressure tank in th...

Page 11: ...EN FOR AUTOMATIC WATER SUPPLY STATIONS When using the control unit in automatic mode as well as in pressure boosting systems it is necessary to take into account that the device is designed for the system maximum summing pressure as 6 bar ...

Page 12: ...12 installation and operation manual FOR SURFACE AND SUBMERSIBLE PUMPS ...

Page 13: ...proof three core electrical cable with double insulation Max size of power cable for connectors XI Х2 and wire nut CИЗ 2 2 5 mm2 Max line length for cables with size of 1 5 mm2 36 m If it is required to extend supply cable by more than 36 m it is necessary to select length and size thereof according to the table below Size of three core cable mm2 1 5 2 5 4 0 6 0 10 0 Max line length m 36 60 95 145...

Page 14: ...e in pressure tanks shall be lower than Pmin by 0 1 0 2 bar It is necessary to check it at least once a month in accordance with Manual for Pre sure Tank 3 Avoid water coming to the control unit housing 4 It is not permissible to use TURBI M2 control unit with upper cover removed 5 Avoid water coming into the pump suction line 6 Avoid water freezing in the device and the system In winter it is nec...

Page 15: ... is not used for a long time in winter it is nec essary to disconnect power supply drain water from it and dismount TURBI M2 control unit Store the device in dry and heated premises away from direct sunlight Permissible storage temperature from 1 to 40 C ...

Page 16: ...p operates con tinuously and does not switch off when water consumption stops Microcontroller failure Contact service center Pump is switched off Sealed contact failure Contact service center Pump is not switched on at the system pressure drop to Рmin and is not switched off at Pmax Pressure sensor failure Open circuit in pressure sensor No contact in pressure sensor terminal Microcontroller failu...

Page 17: ...ace the product provided that consumers comply with the rules of operation Warranty does not provide compensation for material loss or injury resulting from improper installation and operation Warranty liabilities shall not cover the following failure caused by customers non compliance with requirements of the present Installation and Operation Manual improper electric hydraulic and mechanical ins...

Page 18: ...t without any notice to make changes in the product design for the purpose to improve its technological parameters Manufacturer Subline Servise LLC build 1 12 Konovalov str Moscow 109428 Russia Phone 7 495 73491 Name of product To be completed by seller Warranty Card Serial number Date of sale date month year Seller s signature M P To be completed by buyer Buyer s signature Technical support 7 495...

Reviews: