5.SETTING OF FUNCTIONS
35
5-6. Zero Track
Gradual changes in the zero point due to drifts etc., are automatically tracked for
correction.
Setting range
ZT (time): 0.0 - 9.9 sec.
ZT (width): 00 - 99
How to set
・
When displacement of the zero point is within the set count of tracking
and it continues more than the set time, it is automatically made zero by
Zero Tracking function.
・
The time (tracking delay) is set in the range of 0.1 - 9.9 sec., and the
band (tracking band) is set in the range of 01 to 99.
If the time is set at 0.0 sec. and the band at 00, the zero tracking function
does not work.
Boundary of zero track
DELAY
Indicated value
+COUNT
-COUNT
BAND
+
0
-
DELAY
Band=count
×
2
From the point when it returned within the range,
counting will be resumed.
CAUTION
Since the zero track function works from the calibrated zero point of the
indicated value, it does not work if the indicated value is beyond the
track band. In such a case, obtain the zero point again by zero
calibration.
Setting call