Unipower TMN6000 Operating Manual Download Page 25

22

TMN/TMP SERIES

OPERATING MANUAL

20.10 Checking the Other TMN/TMP Modules.  Each module should be tested

in the above manner to verify its operation.  Go back to Section 20.5 and
proceed through the tests one by one until all modules have been verified.

20.11 Checking the Complete Rack.  Confirm that the output voltages of the

individual modules are all accurately set to 24, 28 or 48V. The voltages
between modules should be within ±1% of each other  for best perfor-
mance of the current sharing circuitry.  Insert all modules into the rack.
Connect a power load - - high-power resistor or electronic load in resistive
mode -- in accordance with the table, to the output of the rack.  Connect
the + and - Sense leads to  + and - sides of the load, respectively, as in
Section 20.4.

Table 20-1 TMN/TMP Rack Loads for Test

Note that on the back of the rack each module has its own AC power
connection. For this test each module should be connected to a separate

15A, 230VAC circuit. Plug the rack into the 230VAC power sources.

Check the load voltage with a digital voltmeter.  It should be very close to
24, 28 or 48VDC (±1%), depending on the model tested.  The AC Good

and DC Good LEDs should both be green on each module.

20.12 While the rack is operating, pull Module No. 1 out while monitoring the

output voltage with a digital voltmeter.  The voltage should remain the
same.  Insert the module back into the rack.  Repeat this for each of the
other modules.  This test determines that hot-swapping is functioning

properly in the N+1 redundant mode.

20.13 With all the modules inserted into the rack, check the Enable input for the

entire rack. Disconnect the Remote Enable wire from J1 Pin 1 to Pin 22.

The rack output should turn off and the output voltage should go to zero.

31.5-42A

54-72A

63-84A

37.5-50A

64.5-86A

75-100A

NO. OF

MODULES

3

3

3

3

3

3

48

28

24

48

28

24

OUTPUT

VOLTAGE

LOAD

CURRENT

LOAD

RESISTOR

1.14 - 1.52

0.39 - 0.52

0.29 - 0.38

0.96 - 1.28

0.33 - 0.43

0.24 - 0.32

MODEL

TMN

TMN

TMN

TMP

TMP

TMP

Summary of Contents for TMN6000

Page 1: ...Rights Reserved UNIPOWER Corporation TMNTMP Man2 08 29 01 NORTH AMERICA 3900 Coral Ridge Drive Coral Springs Florida 33065 USA Tel 1 954 346 2442 Fax 1 954 340 7901 sales unipower corp com EUROPE Par...

Page 2: ...ions 6 10 0 Description of Features and Options 9 11 0 Mechanical Specifications 10 12 0 Safety and Industry Standards 10 13 0 Operating Information 11 14 0 Parallel Operation 14 15 0 Rack Control Sup...

Page 3: ...eries Module 7 4 TMN TMP Series Mechanical Dimensions 7 5 Rear Rack Input and Output Connections 12 6 Rated Output Current vs Ambient Temperature 13 7 Remote Sensing Connection 13 8 Parallel Connectio...

Page 4: ...modules while the system is operating The TMN Series operate worldwide with a 85 264VAC input range at 47 63Hz The TMP Series operates with a 170 264VAC input range at 47 63Hz Each module has input po...

Page 5: ...2 TMN TMP SERIES OPERATING MANUAL Figure 1 TMN TMP Series Bulk Power Front End Figure 2 TMN TMP Series Module Block Diagram...

Page 6: ...appable Modules u LED Operating Indicators u Control and Monitoring Interface Signals 3 0 PRODUCT LINE 3 1 Hot Swap Modules 3 2 Rack 4 0 SAFETY WARNINGS 4 1 These hot swap modules and racks have hazar...

Page 7: ...TICULAR PURPOSE As the sole and exclusive remedy under this warranty the manufacturer at its option may repair or replace the non conforming product or issue credit provided the manufacturer s inspect...

Page 8: ...egulates the output voltage and keeps it constant 7 2 Power Factor Correction This high frequency converter circuit switch ing at 45kHz achieves a power factor of 0 99 by forcing the AC input current...

Page 9: ...ime 3 20mS Dynamic Response 4 1 msec Temperature Coefficient 0 02 C Minimum Load 0A Overload Protection Constant Power Limiting Overvoltage Protection Latched Shutdown Active Current Share 10 Differen...

Page 10: ...G MANUAL Figure 4 TMN TMP Series Mechanical Dimensions Figure 3 Front Panel of TMN TMP Series Module HOT PLUG MODULE MATING RACK MOUNT RACK MOUNT 17 20 436 9 3 50 88 9 AC CONNECTION AREA J1 SIGNAL CON...

Page 11: ...an PHYSICAL SPECIFICATIONS Case Material Module Aluminum Rack Mount Steel Finish Rack Mount Powder Coat Gray Dimensions Inches mm Hot Swap Module 3 30 H x 4 90 W x 13 09 D 84 x 124 x 332 3 Module Rack...

Page 12: ...inputs can also be connected together so that the external control voltage adjusts all the module outputs simultaneously If the output power converter overheats the TMN TMP module will automatically s...

Page 13: ...ondi tion This protection is continuous without damage and recovery is automatic when the overload is removed Current limiting begins at about 105 of rated output current The AC Good indicator is a gr...

Page 14: ...on 18 3 and Figure 5 Both positive and negative outputs are floating and isolated from the chassis 13 3 Output Voltage The output voltage of each module is factory set to 24 28 or 48 volts 1 The volta...

Page 15: ...ING MANUAL Figure 5 Rear Rack Input and Output Connections b Uncovered AC Input Connection Area c Top View of DC Output Bus Bars a Rear Connections to Rack MODULE NO AC CONNECTION AREA J1 SIGNAL CONNE...

Page 16: ...13 TMN TMP SERIES OPERATING MANUAL Figure 6 Rated Output Current vs Ambient Temperature Figure 7 Remote Sensing Connection...

Page 17: ...back of the rack See Section 17 for a complete description of these input and output signals 13 8 Alarm Signals Among the control and supervisory signals are two logic alarms for each module AC Good...

Page 18: ...ation is achieved by reserving one module of the total for redundancy For example if two full 19 inch racks are employed with a total of six modules then 5 1 redundancy is achieved and the full load m...

Page 19: ...1 2 3 4 5 6 7 8 9 10 FUNCTION AC Neutral N C 5V 100mA Aux DC Power Good Remote Enable Sense DC Out DC Out DC Out DC Out PIN 21 22 23 24 25 26 27 28 29 30 FUNCTION AC Line N C N C N C Current Share Rem...

Page 20: ...Good 3 20 N C 21 N C 22 Signal Common 23 Sense 24 Remote Adjust 1 25 Remote Adjust 3 J1 A TTL LO sinking 5mA or short to Pin 22 enables turns on all modules in the rack This input is referenced to Si...

Page 21: ...ule or outside the 22 5 29V range for a 24V module the unit has failed or is in current limit This signal is referenced to Signal Common Pin 22 SIGNAL PIN DESCRIPTION 18 0 INSTALLATION 18 1 Mounting S...

Page 22: ...on the TMN TMP Series except for periodic cleaning of dust and dirt around the fans and the ventilation holes A small vacuum nozzle should be used for this 20 0 TMN TMP MODULES AND RACK SETUP AND TEST...

Page 23: ...ire from J1 Pin 1 to Pin 22 The module output should turn off giving zero volts across the load The DC Good LED should go off 20 8 Checking the AC Good and DC Good Outputs Connect the lead of an exter...

Page 24: ...21 TMN TMP SERIES OPERATING MANUAL Figure 11 Checking Remote Adjust Input Figure 10 Checking AC Good and DC Good Outputs...

Page 25: ...his test each module should be connected to a separate 15A 230VAC circuit Plug the rack into the 230VAC power sources Check the load voltage with a digital voltmeter It should be very close to 24 28 o...

Page 26: ...ood LED off AC Good LED on No output DC Good LED off AC Good LED on SYMPTOM POSSIBLE CAUSE No input power Remote Enable in OFF mode Shorted output Overvoltage protection OVP has latched Check connecti...

Reviews: