Introduction
Sageon III Power System
PM990-8800-00, Rev. 9
1-10
Battery voltage .............................................. 75V maximum
Cells (single cell or monoblock) ................... 24 maximum per SBM board
Cell voltage ................................................... 2V, 4V, 6V or 12V (maximum input 3.33V, 6.66V, 10V, and 20V respectively)
Accuracy ....................................................... +/-10mV at 0°C to 40°C
Resolution ..................................................... 5mV per cell (2V, 4V, and 6V ranges)
10mV per cell (12V range)
Sampling interval .......................................... 1-60 minutes
SBM boards .................................................. 4 maximum
Interconnection ............................................. 16-conductor ribbon cable; 30 feet (10m) maximum length
E. Site Monitor
Analog inputs ................................................ 8
Signal range .................................................. 0-5V
Input protection ............................................. Over-voltage and reverse polarity
Signal scaling and alarm levels ..................... Scale factor and low and high alarm thresholds are user programmable at operator panel
Digital inputs................................................. 12
Signal source ................................................. Voltage free contacts
Logic of digital input .................................... User defined from operator panel
Control outputs ............................................. 4
Output signal source
Voltage free form C relay contact; 1A @ 30 Vdc
1.5 PRODUCT SUPPORT
Product support can be obtained using the following addresses and telephone numbers.
Corporate office:
UNIPOWER, LLC
210 N University Dr
Coral Springs, FL 33071
United States
Manufacturing facility:
UNIPOWER, LLC
65 Industrial Park Rd
Dunlap, TN 37327
United States
Manufacturing facility:
UNIPOWER Slovakia SRO
ZLATOVSKA 1279
Business Center 22
91105 Trencin, Slovakia
Phone: +1-954-346-2442
Toll Free: 1-800-440-3504
Web site – www.unipowerco.com
When contacting UNIPOWER, please be prepared to provide:
1.
The product model number, spec number, S build number, and serial number - see the equipment nameplate on the front panel
2.
Your company’s name and address
3.
Your name and title
4.
The reason for the contact
5.
If there is a problem with product operation:
•
Is the problem intermittent or continuous?
•
What revision is the firmware?
•
What actions were being performed prior to the appearance of the problem?
•