![Unipower INV2500 Operating Manual Download Page 6](http://html1.mh-extra.com/html/unipower/inv2500/inv2500_operating-manual_3900484006.webp)
3
INV2500 & INV5000 SERIES
OPERATING MANUAL
u
Low Distortion 50 or 60Hz Sine Wave
u
42 to 56VDC Input
u
Fully Isolated from Battery Input
u
90% Typical Efficiency
u
Up to 300% Surge Capability
u
Powers Reactive Loads
u
Circuit Breaker Input & Output Protection
u
N+1 Redundant Operation
u
19- or 23-Inch Rack Mounting
u
Overtemperature Protection
u
Form C Relay Alarm Contacts
u
LED Status Indicators
u
Mating Connector Kit with INV2500
u
Rear Safety Cover on INV5000
3.0
PRODUCT LINE
Table 3-1
Telecom Inverter
Table 3-2
Inverter Shelf (for INV2500)
4.0
SAFETY WARNINGS
4.1
These telecom inverters have hazardous external and internal voltages. They
should be handled, tested and installed only by qualified technical persons
who are trained in the use of power systems and are well aware of the haz-
ards involved.
4.2
The input and output terminals are at hazardous voltage potentials. Do not
touch these areas when power is applied.
4.3
When operating these inverters, the chassis ground terminal must be con-
nected to safety ground to minimize electrical shock hazard and to ensure low
EMI (electromagnetic interference).
MODEL
INPUT OUTPUT FREQ.
INV2500
48VDC
115VAC@22A
60Hz
INV5000-115/60
48VDC
115VAC@44A
60Hz
INV5000-230/50
48VDC
230VAC@22A
50Hz
INV5000-230/60
48VDC
230VAC@22A
60Hz
MODEL SIZE HEIGHT CAPACITY
INVR2U
19 inches
2U (3.5 Inches)
2 INV2500s