4.15 Rectifier Installation
NOTE
Ensure that the rectifier handle is in the OPEN position (forms 35-40° angle with
rectifier body) before inserting the module into the slot.
Rectifier module should be installed starting from the bottom left position in the rectifier
shelf.
NOTE
If you ordered a power system with 3 rectifier positions, leave the bottom two
slots blank and install the rectifier from the middle left position.
1.
Place the rectifier module in the desired slot with the handle facing out.
2.
Slide the rectifier module into the slot until it contacts the interface connection at the rear
of the shelf, Figure 4-16 1.
3.
Fully insert the rectifier by pushing the handle towards the shelf. The rectifier handle will
rise up and lock the rectifier into the position, Figure 4-16 2.
Repeat steps 1 to 3 for the remaining rectifier modules.
2
1
Figure 4-16 Rectifier Installation