2.0 FEATURES & OPTIONS
2.1
The following is a summary of the important features of the Series.
Thin Height: 1.75 inches (1RU)
19 or 23-Inch Rack Mounting
Dual A/B Loads
Current Capacity: 80 to 150A per Load (Depends on Model)
Operating Voltage: 12, 24 or 48VDC
Positive or Negative Ground
Red/Green LED Indicators
1 Form C Relay Contact per Bus
Protection: GMT Fuses or Magnetic Circuit Breakers
Independent and Isolated Loads
Input Connections: Crimp Type Lugs
Output Connections: Barrier Terminal Strips
Reverse Polarity Protected
2.2
Options. There are three standard options available:
Option C
- Clear plastic rear cover to protect connectors and wiring from damage. This
option will be supplied automatically unless it is specificially requested to be deleted.
Option S
- This option internally links the A bus to the B bus so that a fully configured unit
can be supplied DC from a single feed. The A and B sides have the same voltage and polarity.
3.0 PRODUCT LINE
The following table shows the 3 basic configuration that are available for each type of panel. ‘x’
denotes the voltage and polarity. Full configuration details are given in section 8.
BASE MODEL
INPUT
FEEDS
MAX. #
BREAKERS / FUSES
AMPS
EACH FEED
TOTAL
AMPS
DPBF1U-Ax
1
4 Breakers
150
150
DPBF1U-Ax-Bx-S
8 Breakers
150
150
DPBF1U-Ax-Bx
2
4 + 4 Breakers
96
192
DPGF1U-Ax
1
4 or 6 Fuses
80
80
DPGF1U-Ax-Bx-S
8 or 12 Fuses
80
80
DPGF1U-Ax-Bx
2
4 or 6 + 4 or 6 Fuses
64
128
Table 1. Basic Configurations