UniPOS                                                                                                          Fire Extinguishing Control Panel FS5200E 

 

Service Personnel’s Instruction Manual                                                                                                           page1/2 

Service Personnel’s Instruction Manual for Operating 

Fire Extinguishing Control Panel FS5200E  

 

1. Indications and Buttons  

1 Indicator 

Hold extinguishing

 

2 Indicator 

Fault in a circuit of signal wires

 

3 Indicator 

System Error

 

4 Indicator 

 

Fault in power supply

 

5 Common 

Indicator 

Fault Condition

 

6 Indicator 

 

Manual Mode 

7 Indicator 

Power Supply

 

8 Indicator 

Disabled Component

 

9 Indicator 

Low Pressure 

10 

LCD display (4

х

20) 

11 Indicator 

Automatic Mode 

12 Indicator 

Fire condition stage II – Extinguishing

 

13 Switch 

– 

Automatic / Manual / Disable

 

14 Indicator 

Fire condition stage I

 

15 

Individual indicators of the Fire detecting lines 

16 Indicator 

Disable extinguishing

 

17 Button 

Reset

 

18 Button 

Menu

 

19 Button 

Down

 

20 Button 

Alarm

 with indicator 

Stop alarm

 

21 Button 

Up

 

22 Button 

Outputs 

with indicator 

Suppressed outputs

 

23 Switch 

– 

Access level

  

24 Button 

Cancel

 

 

1  2  3

1 2 3

4 5 6

7

8

9

10

11

12

13 14

15

16 17

19 20

22

24

23

21

18

 

 

Fig.1 

2. Duty Mode 

This is the condition when the fire alarming installation is not in Extinguishing Mode, Fire condition and Fault 

condition. In Duty Mode only the green LED indicator is activated 

 (Power supply) and the yellow indicator 

 

for Manual Mode or 

 Manual Automatic Mode. The local sounder is off. The display shows a message “Fire 

Protect” and information about the current local time. 

 

3. Operation of the personnel on duty in the case of signal for Fault condition 

If any fault condition is registered the sounder of the fire extinguishing control panel produces discontinuous sound 

signal.  

  To stop the sound signal, turn by means of the key the switch (Pos. 23) to position  

 and press button. 

. The LED indicator of the button starts to illuminate and the sounder stops.  

  If the indicators 

 and 

 are lit and a text message “Fault Mains Supply” is displayed check if the 

voltage in the electric board supplying the fire extinguishing control panel is 220 V. If the voltage is restored 
the light indications for fault condition are switched off.  

  Turn the switch to position  

.  

In all other cases when a fault condition is signaled, turn the switch to position 

, press the button 

 

to stop the sound signaling and call the service company.  

 

 