CONVENTIONAL LINE-MONITORING MODULE

Type FD7201

Instruction Manual 01-7201-

11

-0

5

1293

TECHNICAL DATA

Supply voltage of the signal loop

(15-30)V DC

Current of the signal loop in Duty mode

(4-8) mA

Current of the signal loop in Fire condition in the built-in detector

5

 mA at 24 VDC

Current of the signal loop in Fire condition in a detector integrated
in the conventional fire alarm line

(8-50) mA 

-

Voltage of the conventional fire alarm line

(15-30)V DC

Current of the conventional line when registered:

- Break in a line

(

0-2

 mA  

- Duty mode

(

2

-

10

) mA

- Fire condition

(

10

-50) mА

- Short circuit

higher than 50 mA

Area protected by the built-in rate of rise heat detector

c

ircle with

 

diameter 10m 

at h<8m

2

Maximum cross-section of the connecting wires

2,5 mm

Type of the connecting wires

- signal loop

two-wire, shielded 

- conventional fire alarm line

two-wire

Degree of protection

IP 43

Operational temperature range

minus 10

°

С - plus 55

°

С

Relative humidity resistance

(93 ±3)% at 40

°

С

Dimensions (base incl.)

Ø100 mm, h 47mm

Weight

0,100 kg 

INSTALLATION

     Conventional line monitoring module type FD7201 shall be mounted onto base type 7100А. To install the 
module and its base please follow the sequence:
    1.

 

Fix the base on the ceiling of the protected premises using appropriate fixings.

    2.Complete the wiring as shown on fig. 2 and in accordance with the construction projects of the site. Terminate 
the conventional fire alarm line using the provided terminating component.
   

Note

:  We recommend you to install diodes on the bases of all conventional fire detectors. Otherwise in case of 

a removed conventional detector the module will indicate break in the conventional line.
   3.

 

Replace the conventional line-monitoring module on the base and rotate it in a clockwise direction to reach 

the base's leading channels (Fig.1.1, position 2). Continue rotating in a clockwise direction to complete location 
(Fig.3.1). The bench marks of the module and the base should fully coincide (Fig. 3.2). 
   4. To lock the module to the base separate the key from the base (Fig. 1.2, position 9) and keep it in a safe place, 
cut the technological edge (Fig. 1.2, position 7) of the click (Fig. 1.2, position 8) and complete the instructions 
described above. 
   5. To unlock the module insert the key into the slot, according to Fig.4, rotate the module anticlockwise until rest, 
take the key out and continue rotating to release the module. 

TESTING THE CONVENTIONAL LINE-MONITORING MODULE

   Test the module with conventional detectors connected, and after connecting the module to fire control panel 
type IFS7002 as a part of the site's fire alarm system.
   1. Set the control panel to Duty mode. The conventional line-monitoring module shall enter Duty mode and shall 
indicate the condition accordingly, as described above. 
   2. Set the built-in heat detector or

 set 

 any detector connected to the module's conventional line, to Fire 

condition. The module shall indicate the condition accordingly, as described above.
   3. Send a reset command from the fire control panel IFS7002 to the conventional line-monitoring module. The 
module shall restore the Duty Mode

twice

GENERAL DESCRIPTION

    

Conventional line-monitoring module 7201 is designed to connect up to 32 conventional fire detectors to an 

addressable fire alarm control system type IFS7000 and to monitor the protected area through a built-in rate of 
rise heat detector.

   

Fire  control  panel  IFS7002  is  able  to  exchange  information  with  the  module  through  a  specialized 

communication protocol UniTALK and supplies power to the module via its signal loop. The status of the signal 
loop is monitored through a short circuit isolator built-in the conventional line monitoring module.
The unit comprises a printed circuit board and a heat chamber (fig.

1

  pos.

4

 ) placed in a plastic body (fig.

1

 pos.

5

). 

Terminals for connection to the signal loop

 –IN/OUT

,

 +IN

 (fig.

1

 pos.

8

) and for conventional detectors line 

RI/KL-

KL+

 (fig.

1

pos.

7

) are provided on the base type 

7100A

 (fig.

1

pos.

1

). The module is completed with a terminating 

component 

EOL-

1

 having a red 

R

 and a black 

B

 leads (fig.

1

 pos.

9

) that shall terminate the conventional fire alarm 

line. 

    

The red and yellow LEDs situated on the body of the module (fig. 

1

 pos.

3

) provide information for the following:

Duty mode

 - both LEDs flash every 16 seconds;

Built-in detector in Fire condition

 – the red LED illuminates continuously;  the yellow LED is extinguished;

Fire detector in the conventional line in Fire condition

 – the red LED flashes repeatedly 

every

 1 sec., the 

yellow LED is extinguished;

Activated short circuit isolator for the signal loop

 – the red LED is extinguished; the yellow LED flashes 

repeatedly 

every

 1 sec;

Removed fire detector in the conventional line

 - the red LED is extinguished; the yellow LED produces double 

flashing light, repeatedly 

every

 1 sec;

Short  circuit  or  break  in  the  conventional  line

  -  the  red  LED  is  extinguished;  the  yellow  LED  produces 

continuous light.

WARRANTY

   

The warrant period is 36 months from the date of purchase. The manufacturer guarantees the normal 

operation of the unit providing that the requirements set herein have been observed. The manufacturer does 
not bear warranty liabilities for damages caused through accidental mechanical damage, misuse, adaptation 
or modification after production. The manufacturer bears warranty liabilities for damages in the fire detector 
caused through manufacturer's fault only.

Manufacturer: UniPOS Ltd., 114 Grenaderska Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com

SERVICE SCHEDULE

T

able 1

Task description

Periodicity

1.

Inspection for visible physical damage

weekly

2.

Satisfactory operation test in real conditions

monthly

3*

Check and clean dust contamination

every 6 months

4.

Check and clean base and head contacts and connections

Annually

* To complete task №3, remove the detector's upper part (Fig. 1, position 6). Clean using a small 
brush. The upper part is removed by rotating it anticlockwise until rest.