xxxx
Manual call point
with build short circuit isolator
TYPE
FD7150М
INSTRUCTION MANUAL
02-7150М-09-20
GENERAL DESCRIPTION
The manual call point FD7150М is designed for indoor installation as a component of an Addressable Fire
Alarm System IFS7000М series.
The unit is compatible with the requirements of the European Standard EN54-11:2001/A1:2005, EN54-17:2005/AC:2007.
Unpacking of the manual call point is shown in the sequence of steps: Pos.1and 2 Fig. 2.
The FD7150М manual call point has a built-in short circuit isolator for the signal loop.
All statuses from FD7150M are send and visualised on the control panel.
TECHNICAL DATA
Minimum operating voltage
18V DC
Nominal operating voltage
24V DC
Maximum operating voltage
30V DC
Current consumption in duty mode
290+/-30uA
Electrical Installation
Through terminal for connecting
wires
with
cross-section
(0,5-1,5)
mm2
Application
INDOOR USE, TYPE A (direct operation)
Operational temperature range
From minus 10°С to plus 55°С
Relative humidity resistance
(93±3)% at 40°С
Dimensions
98х96х51
mm
Weight
0.150kg.
Material ABS
п
INSTALLATION
To install the manual call point, please refer the sequence of steps from 1 to 9 shown on fig.2:
Detailed wiring diagram is shown on fig.1
Terminal – “E“ shield of the signal loop;
Terminal – “+“ of the signal loop;
Terminal – “-” of the signal loop;
Terminal – “-” of the signal loop;
Terminal – “+” of the signal loop;
Terminal – “E“ shield of the signal loop;
TESTING
The manual call point is tested as a part of the Addressable Fire Alarm System (IFS7000M) or on service schedule.
1. Теst procedure
1.1.Power supply the manual call point from the signal loop as showed on pos.7 of fig. 2
1.2. Press the manual call point on the specific place till showing of the yellow thumb of the actuators pos.2, fig 3.
1.3. The manual call point is activated - in “Alarm mode”.
2. Reset to duty mode:
To reset the manual call point to duty mode, please refer the sequence pos. 3;4 and 5 of fig. 3
The reset key must be rotate clockwise to retract two yellow thumb
of the actuating member pos 4, fig 3.
SERVICE SCHEDULE
a
1.Inspection for visible physical damage
- weekly
2. Trigger on standard operation scenario
- monthly
WARRANTY
a
The warranty period is 36 months from the date of purchase.
The manufacturer guarantees the normal operation of the unit providing that the requirements set herein have been observed.
The manufacturer does not bear warranty liabilities for damages caused through accidental mechanical damage,
misuse, adaptation or modification after production.
The manufacturer bears warranty liabilities for damages in the unit caused through manufacturer's fault only.
Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria,
http://www.unipos-bg.com