background image

 

xxxx

Manual call point 

with build short circuit isolator 

TYPE 

FD7150М

INSTRUCTION MANUAL

                  02-7150М-09-20

 

GENERAL DESCRIPTION

The manual call point FD7150М is designed for indoor installation as a component of an Addressable Fire

Alarm System IFS7000М series.

The unit is compatible with the requirements of the European Standard EN54-11:2001/A1:2005, EN54-17:2005/AC:2007.

Unpacking of the manual call point is shown in the sequence of steps: Pos.1and 2 Fig. 2.

The FD7150М manual call point has a built-in short circuit isolator for the signal loop.

All statuses from FD7150M are send and visualised on the control panel. 

TECHNICAL DATA

Minimum operating voltage   

 

18V DC

Nominal operating voltage 

 

 

24V DC

Maximum operating voltage   

 

30V DC 

Current consumption in duty mode 

 

290+/-30uA

Electrical Installation   

 

 

Through terminal for connecting

      wires 

with 

cross-section 

(0,5-1,5) 

mm2

Application 

 

 

 

 

INDOOR USE, TYPE A (direct operation)

Operational temperature range  

 

From minus 10°С to plus 55°С

Relative humidity resistance 

 

 

(93±3)% at 40°С

Dimensions 

    98х96х51 

mm

Weight 

     0.150kg.

Material     ABS

п

INSTALLATION

To install the manual call point, please refer the sequence of steps from 1 to 9 shown on fig.2: 

Detailed wiring diagram is shown on fig.1

 

   Terminal – “E“ shield of the signal loop;

 

… Terminal – “+“ of the signal loop;

 

… Terminal – “-” of the signal loop;

 

… Terminal – “-” of the signal loop;

 

… Terminal – “+” of the signal loop;

 

… Terminal – “E“ shield of the signal loop;

TESTING

The manual call point is tested as a part of the Addressable Fire Alarm System (IFS7000M) or on service schedule.

1. Теst procedure

     1.1.Power supply the manual call point from the signal loop as showed on pos.7 of fig. 2

     1.2. Press the manual call point on the specific place till showing of the yellow thumb of the actuators pos.2, fig 3.

     1.3. The manual call point is activated - in “Alarm mode”. 

2. Reset to duty mode:

To reset the manual call point to duty mode, please refer the sequence pos. 3;4 and 5 of fig. 3

    

                                            

The reset key must be rotate clockwise to retract two yellow thumb 

                                                                                 of the actuating member pos 4, fig 3.

SERVICE SCHEDULE

a

1.Inspection for visible physical damage   

- weekly

2. Trigger on standard operation scenario 

- monthly

WARRANTY

a

The warranty period is 36 months from the date of purchase.

The manufacturer guarantees the normal operation of the unit providing that the requirements set herein have been observed.

The manufacturer does not bear warranty liabilities for damages caused through accidental mechanical damage,

 misuse, adaptation or modification after production. 

The manufacturer bears warranty liabilities for damages in the unit caused through manufacturer's fault only.

Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria, 

http://www.unipos-bg.com