background image

4

Document 52017  NION-MXL Instruction Manual Rev. A  10/10/02

WARNING 

Several different sources of power can be con-

nected to the fire alarm control panel.  Disconnect all sources of
power before servicing.  Control unit and associated equipment
may be damaged by removing and/or inserting cards, modules,
or interconnecting cables while the unit is energized.  Do not
attempt to install, service, or operate this unit until this manual is
read and understood.

CAUTION - 

System Reacceptance Test after Software

Changes.  To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any
programming operation or change in site-specific software.  Re-
acceptance testing is required after any change, addition or de-
letion of system components, or after any modification, repair or
adjustment to system hardware or wiring.

All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.  In
addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.

This system  meets NFPA requirements for operation at
0-49° C/32-120° F

 

 and at a relative humidity of 85% RH - 93%

per ULC - (non-condensing) at 30°

 

C/86° F.  However, the useful

life of the system's standby batteries and the electronic compo-
nents may be adversely affected by extreme temperature ranges
and humidity.  Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal
room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and
indicating device loops.  Most devices cannot tolerate more than
a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may

operate erratically or can be damaged when subjected to light-
ning-induced transients.  Although no system is completely im-
mune from lightning transients and interferences, proper ground-
ing will reduce susceptibility.  

Overhead or outside aerial wiring

is not recommended, due to an increased susceptibility to
nearby lightning strikes.  Consult with the Technical Services
Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or in-
serting circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure.  When possible, make all
cable entries from the sides or rear.  Before making modifica-
tions, verify that they will not interfere with battery, transformer,
and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal re-
moval.

Though designed to last many years, system components
can fail at any time.  This system contains static-sensitive com-
ponents.  Always ground yourself with a proper wrist strap be-
fore handling any circuits so that static charges are removed
from the body.  Use static-suppressive packaging
to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and
programming manuals.  These instructions must be followed to
avoid damage to the control panel and associated
equipment.  FACP operation and reliability depend upon proper
installation by authorized personnel.

WARNING: This equipment generates, uses, and can radiate
radio frequency energy and if not installed and used in accor-
dance with the instruction manual, may cause interference to
radio communications.  It has been tested and found to com-
ply with the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is designed to pro-
vide reasonable protection against such interference when
operated in a commercial environment.  Operation of this
equipment in a residential area is likely to cause interference,
in which case the user will be required to correct the interfer-
ence at his own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des Com-
munications du Canada.

FCC Warning

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

Precau-L-4-2002.p65

Acclimate Plus™HARSH™NOTI•FIRE•NET™ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER®.
NION™ and UniNet™ are trademarks of NIS.  NIS™ and NOTIFIER® Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite
Alarms, Inc.  Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation.  ARCNET® is a registered trademark of Datapoint
Corporation.  Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.  LEXAN® is a registered trademark of GE Plastics, a subsidiary
of General Electric Company.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for 2000 NION-MXL

Page 1: ...UniNet 2000 NION MXL Instruction Manual NION MXL Document 52017 10 10 02 Rev A Version2 52017 A ECN 02 232 Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...2 Document 52017 NION MXL Instruction Manual Rev A 10 10 02 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 3: ...scaping gas improper storage of flammable mate rials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detec tors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qu...

Page 4: ...difica tions verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal re moval Though designed to last many years system components can fail at any time This system contains static sensitive com...

Page 5: ...2 Serial Communication DIP Switch Configuration 11 Figure 2 2 Switch S2 Settings for the NION 232B RS 232 Configuration 11 2 3 Configuring the MXL Panel for Communications 12 Figure 2 3 MXL Panel Settings 12 2 4 Device Addressing for the MXL Control Panel 12 2 5 Software Replacement Upgrade Installation 12 Figure 2 4 NION Software Replacement 12 Section 3 Plug In Configuration and Operation 13 3 1...

Page 6: ...and other data originating from an MXL panel This system is suitable for proprietary systems listed under NFPA 72 1993 Proprietary Service UniNet consists of graphical workstations monitoring and controlling local or remote twisted pair or fiber optic networks Remote network monitoring is achieved through the use of a Building Communications Interface BCI which has a maximum capacity of 32 nodes E...

Page 7: ... provides a single two way communication channel for EIA 232 serial data when connected to a control panel NIONs are specific to the type of network to which they connect FT 10 or fiber The transceiver type must be specified and ordered separately when ordering the NION For information regarding network transceivers see the 51539 Network Installation manual section 1 1 3 The NION can be powered by...

Page 8: ...losure NISCAB 1 The following paragraphs describe all required and optional components used to assemble a functional NION MXL All of the items described must be ordered separately NISCAB 1 Installation The NION 232B may be mounted stand alone in a single node enclosure the NISCAB 1 where power is supplied by the monitored equipment or an external source This enclosure is provided with door and key...

Page 9: ...e set to 8 data bits with either Even or Odd parity 1 7 NION Power Requirements Connection The NION 232B requires 24VDC 10 0 080 A nominal and battery backup in accordance with local code requirements It can be powered by any power limited filtered source with battery backup which is UL or ULC listed as appropriate for your area for use with fire protective signaling units All connections must be ...

Page 10: ...und Yellow This LED provides information on node binding by one of the three modes listed below Off NION is bound Flashing NION is not bound Solid NION is in a fault condition or the PROM chip is not installed Net Receive Green Flashes once when receiving a message from the Echelon network Serial Receive Green Flashes once when receiving an event message from the fire panel Serial Fail Yellow This...

Page 11: ...ion 2 NION MXL Configuration 2 2 2 Serial Communication DIP Switch Configuration The baud rate parity and data bits of the NION 232B must be equal to those of the RS 232 serial port of the control panel The NION 232B settings must be configured in the field for the application it was ordered to fill These settings are made on switch S2 If it becomes necessary to change any of these settings use th...

Page 12: ... Enable De Energize and Disable Energize commands a device must be manually created in the Worksta tion with device ID RlyXXXYY where Rly is the prefix for a relay device type XXX is the loop number and YY is the address 2 5 Software Replacement Upgrade Installation When replacing or upgrading the NION software chip execute the following steps 1 Disconnect all power to the NION 232B IMPORTANT Alwa...

Page 13: ...is installed There may be occasions however when a plug in will need to be configured manually This is done using the NION Plug In Application Selection and Configuration form To access this form from the Workstation select Workstation Configuration NION Applications To configure the NION MXL Plug In follow these steps 1 Select MXL in the NION Type combo box Menu Items Commands Available for Curre...

Page 14: ... plug in applications to function they must be linked with the nodes or devices to which they corre spond In most cases this is done automatically and each recognized node is linked to the appropriate plug in application There may be times when nodes and devices are not automatically read and updated by the workstation and links are not established Therefore it is advised that this one time linkin...

Page 15: ...er typing the password and hitting Enter you will have access to online commands see Figure 3 5 Figure 3 4 Online Panel Session Menu Bar Options File Close This will exit the plug in i e the online panel session screen Configure Set Password The default password is 44444 IMPORTANT This password must be set to corre spond to the password of the MXL panel Command Clear Screen This clears the panel s...

Page 16: ... Power report m PSR 1 or MMB 1 module number LAV m List Analog Voltage m module number MLT m MOI 1 Lamp test LTV m List Threshold Voltage m module number DEV m d x Device LED Control m module number d sub address device LED x E for energize LED D for de energize LED LMT m List Module Type m module number LDT m List Device Type m device number LMS m List Messages m module number LSW List Software V...

Page 17: ...Description 13 Launching 15 Mapping 14 MXL Panel Configuring 12 Device Addressing 12 MXL Panel Settings 9 N NION Power Requirements 9 NION 232B Board Layout 7 NION 232B Board Layout 7 NION 232B Operation 10 NION 232B Pwoer Requirements 9 NION SPB Software Replacement 12 NISCAB 1 8 NISCAB 1 Installation 8 Node Information 14 O Online Panel Session 15 Menu Bar Options 15 Online Panel Session Command...

Page 18: ...18 Document 52017 NION MXL Instruction Manual Rev A 10 10 02 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 19: ...19 Document 52017 NION MXL Instruction Manual Rev A 10 10 02 This page intentionally left blank Technical Manuals Online http www tech man com firealarmresources com ...

Page 20: ... Fire Lite Place Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that NOTIFIER is not an insurer and assumes no ris...

Reviews: