240
Repetition in the event of loss of flame during operation
Edit
0
2
1
0 SO
OEM
0 = None
1 = None
2 = 1 x Repetition
241.00
Valve
proving
Edit
0
1
1
1 SO
OEM
0 = Off
1 = On
241.01
Valve
proving
Edit
0
1
1
0 SO
OEM
0 = During prepurge time (t1)
1 = During postpurge time (t8)
241.02
Valve
proving
Edit
0
1
1
0 SO
OEM
0 = According to P241.01
1 = During prepurge time (t1) and postpurge time (t8)
242
Valve proving test space evacuating
Edit
0 s
2.648 s
0.147 s
2,646 SO
OEM
243
Valve proving time test atmospheric pressure
Edit
1.029 s
37.485 s
0.147 s
10,290 SO
OEM
244
Valve proving test space filling
Edit
0 s
2.648 s
0.147 s
2,646 SO
OEM
245
Valve proving time test gas pressure
Edit
1.029 s
37.485 s
0.147 s
10,290 SO
OEM
254
Response time detector error
Edit
0
1
1
0 SO
OEM
0 = 1 s
1 = 3 s
257
Gas: Postignition time (t3n – 0.3 seconds)
Edit
0 s
13.23 s
0.147 s
2,205 SO
OEM
259.00
Opening time of actuator (t11) (timeout for lockout)
Edit
0 s
1237 s
4.851 s
67,914 SO
OEM
259.01
Opening time of actuator from ignition load to low-fire position
Edit
0 s
37.485 s
0.147 s
14,994 SO
OEM
259.02
Opening time of actuator from low-fire to ignition load position
Edit
0 s
37.485 s
0.147 s
14,994
260
Closing time of actuator (t12) (timeout for lockout)
Edit
0 s
1237 s
4.851 s
67,914 SO
OEM
500
Ratio control
515
Actuator position during prepurge time (t1) and postpurge time (t8)
Edit
0
1
1
1 SO
OEM
0: Purging in low-fire
1: Purging in high-fire
560
Pneumatic combustion control
Edit
0
2
1
1 SO
SO
0 = off / 3-step modulation
1 = PWM fan / analog modulation
2 = air damper / analog modulation (feedback potentiometer ASZxx.3x
required)
21