![Unigas K990A Installation Manual Download Page 6](http://html1.mh-extra.com/html/unigas/k990a/k990a_installation-manual_3965542006.webp)
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Fuel
Fuel
The burner technical specifications, described in this manual, refer to natural gas (calorific net value H
i
= 9.45 kWh/Stm
3
, density
ρ
=
0.717 Kg/Stm
3
). For different fuel such as biogas, multiply the values of flow and pressure by th corrective factors shown in the table
below.
For example, to obtain the flow and pressure values for the biogas:
Type
K750A
Model
M-
MD. SR.
*
A. 1.
80.
EI.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
1 BURNER TYPE
K750A, K890A, K990A
2 FUEL
M - Natural gas
L - LPG
3 OPERATION (Available versions)
PR - Progressive
MD - Fully modulatingFully modulating
4 BLAST TUBE
SR = Standard blast tube + ABS polymer (silenced) air intake
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard
Y - Special
7 EQUIPMENT
1 = 2 gas gas proving system
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
65 = DN65 80 = DN80 100 = DN100 125 = DN125
9 MICRO-PROCESSOR CONTROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
EK = with O
2
trim control, with VSD control
DANGER! The burner must be used only with the fuel specified in the burner data
plate.
Fuel
H
i
(KWh/Stm
3
)
ρ
(kg/Stm
3
)
f
Q
f
p
Biogas
6,395
1,1472
1,478
3,5
ATTENTION! The combustion head type and the settings depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .
ATTENTION! The corrective factors in the above table depend on the gas composition, so on the calorifc value and
the density of the gas. The above value can be taken only as reference.
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --
Q
biogas
Q
naturalGas
1 478
=
p
biogas
p
naturalGas
3 5
=
Summary of Contents for K990A
Page 41: ...PART IV MAINTENANCE 41...
Page 42: ......
Page 43: ......
Page 45: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 52: ...8...
Page 56: ...12 2 2 LMV5x program structure...
Page 83: ...39...
Page 90: ......
Page 91: ......
Page 92: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 94: ...Annex1 Example for motor cable...
Page 95: ......
Page 96: ...Annex 2 Example for sensor cable...
Page 97: ......
Page 98: ......
Page 102: ......