Correct electrodes positioning
To guarantee a proper ignition, the measures shown in the following pictures must be observed.
Ensure the
VE
locking screw of the electrodes group is tight before refitting the burner.
Checking the detection current
If the burner locks, perform the following inpesctions. To measure the detection signals refer to the diagrams in the next picture. If the
signal is less than the value shown, check the position of the detection electrode, the electrical contacts and if necessary replace the
detection electrode.
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner’s main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel cock of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
z
Standard burner
z
Low NOx burners
E
190
7
E
2÷3
Connector
µA DC SCALE
2
Detection electrode
Flame
Control box
Minimum detection signal
Siemens LME11
3 µA