6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical specifications
Note:
the Output values are referred to comburent air temperature lower than 50°C.
NOTE ON THE BURNER WORKING SERVICE:
for safety reasons, one controlled shutdown must be performed every 24 hours of
continuous operation.
Type
HTLX520.1
Model
MG. MD. S. *. E. 1. 65. ES.
(1)
(2) (3) (4) (5) (6) (7) (8)
(9)
(1) BURNER TYPE
HTLX92R, HTLX92.1,
HTLX512.1, HTLX515.1,
HTLX520.1
(2) FUEL
MG - Natural gas-Light oil
(3) OPERATION
PR - Progressive
MD - Fully modulating
(4) BLAST TUBE
S - Standard L = Extended blast tube
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A - Standard
Y - Special
E- Junction box
(7) EQUIPMENT
1 = 2 gas proving system
8 = 2 gas proving maximum pressure switch
(8) GAS CONNECTION
50 = Rp2
-
65 = DN65 - 80 = DN80 - 100 = DN100
(9) MICRO-PROCESSOR CON-
TROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
EK = with O
2
trim control, with VSD control
BURNER TYPE
HTLX92R
HTLX92.1
HTLX512.1
HTLX515.1
HTLX520.1
Output
min - max kW
340 - 2700
650 - 3650
700 - 4500
580 - 5900
650 - 6800
Fuel
MG - Natural gas-Light oil
Gas category
(see next paragraph)
Gas rate
min.-max. (Stm
3
/h)
36 - 286
69 - 386
74 - 476
61 - 476
69 - 720
Gas pressure
(see Note 2)
Oil viscosity
cSt @ 40°C
2 - 7,4
Oil density
kg/m
3
840
Oil rate
min.-max. (kg/h)
29 - 228
55 - 308
59 - 379
49 - 379
55 - 573
Power Supply
400V 3N~ 50Hz
Pump motor
kW
1,1
1,5
Total power consumption
kW
1,6
2
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
ØValves / Connection
2” / Rp 2
Gas train 65
2” 1/2 / DN65
Gas train 80
3” / DN80
Gas train 100
4” / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Continuous
Note1:
all gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas (net calo-
rific value H
i
= 34.02 MJ/Stm
3
).
Note2:
Maximum gas pressure = 360mbar (with Dungs MBC gas valves).
= 500mbar (with Siemens VGD gas valves / Dungs MBC gas valves)
Minimum gas pressure = see gas curves.
Summary of Contents for HTLX92R
Page 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 64: ...8...
Page 68: ...12 2 2 LMV5x program structure...
Page 95: ...39...
Page 102: ......
Page 103: ......
Page 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 106: ...Annex1 Example for motor cable...
Page 107: ......
Page 108: ...Annex 2 Example for sensor cable...
Page 109: ......
Page 110: ......
Page 114: ......