Uniflair CAL 0251 Instruction Manual Download Page 6

11

The adjustment of the pressure switches is co-ordinated in
order to obtain ‘quasi proportionality’ of the fan speed as the
pressure varies.

The VARICOND  system is contained in a metal enclosure fixed
to the side of the condenser and it is suitable for outside
temperatures down to -20°C.
The adjustment of each single pressure switch is carried out as
described in the preceding paragraph ‘ON/ OFF PRESSURE
SWITCH’.

Recommended set point values (factory preset):

SET

DIFF

P1

0V  

100V

16,6 bar

3,1 bar

P2

100V  

130V

20,3 bar

5,7 bar

P3

130V  

160V

21,8 bar

3,0 bar

P4

160V  

230V

23,5 bar

2,7 bar

BEFORE CARRYING OUT ANY WORK ENSURE THE
ISOLATOR IS SWITCHED OFF
                  (switch in position “O”).

MAINTENANCE

  Regularly check the state of the condenser fins;  remove

from them all foreign objects (leaves, feathers, seeds, dust,
etc.)  using a jet of water or compressed air.

The heat exchanger fins are made of thin
aluminium sheet and can cause cuts in the event
of the accidental contact.

  Check that the operation and current absorbed by each fan

is normal  and without any unusual noises;

  Check that the control device is operating normally (see

section CONTROL DEVICES - ADJUSTMENT).

FAULT FINDING

WARNING: BEFORE WORKING ON THE CONDENSER READ CAREFULLY THE SAFETY NOTES AT
THE BEGINNING OF THIS MANUAL.

Operation of the condenser is strictly linked to the working
conditions of the unit to which it is connected and therefore
possible faults which may apparently be attributed do the

condenser could actually be caused by external factors. The
following table lists the most likely faults.

FAULT

POSSIBLE CAUSE

CHECK/ CORRECTIVE ACTION

HIGH DISCHARGE PRESSURE:

A)  The heat exchanger fins are dirty
or blocked by foreign objects

Clean the condenser fins following the instructions in the
section ‘MAINTENANCE’

REFRIGERANT 

CIRCUIT

B)  Cooling air temperature to
condenser too high

1)  Check for potential short circuiting of condenser
cooling air

HIGH PRESSURE SWITCH
TRIPS

2)  Check the value of the actual cooling air temperature
against the design value for the project

(not dependent on causes external
to the condenser such as:

C) Lack of condenser air flow

Check that the condenser is installed with the minimum
clearances specified (see section ‘INSTALLATION’)

  non condensing gases in the

circuit

  valves partially closed in the

section of pipe between the
compressor and the
condenser

D)  One or more fans out of service

Check  for  motor  internal  protection  tripped  and  if
necessary replace the fan motor

  suction pressure too high

 circuit  overcharged  with

refrigerant with excessive sub-
cooling at the condenser )

E)  Control device out of adjustment
or faulty

Check and adjust if necessary the control device (see
section ‘ CONTROL DEVICES - SETTING ‘);  replace if
necessary

LOW DISCHARGE PRESSURE

A)  Control device out of adjustment
or faulty

Check and adjust if necessary the control device (see
section ‘ CONTROL DEVICES - SETTING ‘);  replace if
necessary

B)  Refrigerant leak

Locate and rectify the leak and recharge with refrigerant

Summary of Contents for CAL 0251

Page 1: ...fore installing or servicing the unit read the instructions and the safety notes carefully BEDIENUNGSANLEITUNGEN ACHTUNG Bitte vor Installation oder jeglichem Eingriff an diesem Ger t die Bedienungs a...

Page 2: ...to Holding Legs St tzbeine Pieds de support Patas 4 Connessioni frigorifere Connections Anschl sse Raccordements Conexiones 5 Sezionatore Mains Isolator Hauptschalter Sectionneur Interruptor 6 Regolat...

Page 3: ...he condenser to the nearest possible point to the actual installation location by using a pallet truck or a forklift securing the unit to ensure that it does not fall off Carefully cut or remove the s...

Page 4: ...g diagram SECA attached The condenser can be operated automatically and autonomously as a function of the refrigerant pressure and therefore its power supply does not necessarily have to come from the...

Page 5: ...seldom fall below 0 C In cold climates it could cause excessive hunting of the system Fig 6 The values of SET and DIFF are adjusted by means of the adjusting screws which are accessed by removing the...

Page 6: ...fore possible faults which may apparently be attributed do the condenser could actually be caused by external factors The following table lists the most likely faults FAULT POSSIBLE CAUSE CHECK CORREC...

Page 7: ...3 Verificare che sia presente la guarnizione bianca in teflon B sull attacco rotalock A 4 Avvitare il giunto C sull attacco A GB 1 Unscrew the yellow cap E on the rotalock connection A 2 Remove the b...

Reviews: