4

                                                                                                                         Unidrive M200 / M201 Quick Start Guide

Issue Number: 1

6

Running the motor

This section takes a new user through all the essential steps to running a motor for the first time. Section 4 
provides the minimum connections required to connect and run a motor. The most commonly used 
parameters are shown on the terminal cover of the drive.

0478-0038-01

Action

Detail

Before power up

Ensure:

The drive enable signal is not given, terminal 11 is open

The run signal is not given, terminal 12/13 is open

The motor is connected to the drive

The motor connection is correct for the drive 

Δ

 or Y

The correct supply voltage is connected to the drive

Power up the drive

Ensure:

The drive displays: Inh

Enter minimum and 
maximum speeds

Enter:

Minimum speed Pr 

00.001

 (Hz)

Maximum speed Pr 

00.002

 (Hz)

Enter accel and 
decel rates

Enter:

Acceleration rate Pr 

00.003

 (s/100 Hz)

Deceleration rate Pr 

00.004

 (s/100 Hz)

Enter motor 
nameplate details

Enter:

Motor rated current in Pr 

00.006

 (A)

Motor rated speed in Pr 

00.007

 (rpm)

Motor rated voltage in Pr 

00.008

 (V)

Motor rated power factor in Pr 

00.009

If the motor is not a standard 50/60 Hz motor, set Pr 

00.039

 

accordingly

Ready to autotune

Autotune

The drive is able to perform either a stationary or a rotating autotune. 
The motor must be at a standstill before an autotune is enabled. 

To perform an autotune:

Set  Pr 

00.038 

= 1 for a stationary autotune or set Pr 

00.038

 = 2 

for a rotating autotune

Close the drive enable signal (terminal 11). The drive will display 
’Rdy’.

Close the run signal (terminal 12 or 13). The lower display will 
flash ’tune’ while the drive is performing the autotune.

Wait for the drive to display ‘Inh’ and for the motor to come to a 
standstill. 

Remove the drive enable and run signal from the drive.

Autotune complete When the autotune has been completed,

 

Pr 

00.038

 will be set to 0 

Save parameters

Save parameters

Select ‘SAVE’ in Pr 

mm.000 

(alternatively enter a value of 1000) and 

press the 

Stop / Reset button to save parameters.

Ready to run

Run

The drive is now ready to run the motor.

Increasing and 
decreasing speed

Turning the speed potentiometer will increase and decrease the 
speed of the motor.

Stopping

To stop the motor under ramp control, open either the run forward or 
run reverse terminal. If the enable terminal is opened while the motor 
is running, the motor will coast to a stop.

Pr 02

t

Pr 01

100Hz

Pr 03

t

Pr 04

Mot X XXXXXXXXX

No XXXXXXXXXX  kg

IP55      I.cl F     C  40  s S1

°

V

Hz min

-1

kW cos

φ

A

230

400

50 1445 2.20 0.80 8.50

4.90

CN = 14.5Nm

240

415

50 1445 2.20 0.76 8.50

4.90

CN = 14.4Nm

CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN

I.E.

C

 3

4

 1

(8

7

)

cos 

σ

L

S

R

S