34
Default
Individual values
Value range
Description
10 - 800 HOURS
SEQUENCE CHANGE
200 HOURS
00 min - 30 min
CYCLE BLOCK
00 min
00 - 01
BOILER COOLING FUNCTION
00
30°C - 120°C
BOILER COOLING TEMPERATURE
95
00 - 06
HS 1 TYPE
06
01 - 03
HS 2 STORAGE TANK
01 - 01 - 02
BUFFER
00, 01 (OFF / ON)
SCREED
00
00
00 OFF
00 - 04
HS 1 BUS
04
00 - 05
HS 2 TYPE
00
** see note
SCREED PROGRAM
2K - 20K
HYSTERESIS BURNER 2
2K
* Set value of first stage of first boiler at 1, in the second leave dashes.
All other boiler stages must be disabled.
** See E8.5064 heating controller instruction book
Default
Individual values
Value range
Description
DOMESTIC HOT WATER PRODUCTION
00 - 01 (OFF / ON)
CHARGE PUMP
01 (ON)
00 , 01, 02, 03
PARALLEL PUMP RUNNING
01
00K - 50K
T DHW
20K
5K - 30K
DHW HYSTERESIS
5 degrees
00 min - 30 min
DHW FOLLOWUP
00 min
00, 01 (OFF / ON)
THERMOSTAT INPUT
00 OFF
00, 01 (OFF / ON)
THERMOSTAT FUNCTIONING
00 OFF
Exit level using
RETURN
00, 01 (OFF / ON)
LOAD THROUGH
00 OFF
Default
Individual values
Value range
Description
HEATING CIRCUIT 1
00 - 04
HEATING CIRCUIT FUNCTION
0
00 - 03
PUMP MODE
0
5 - 25
MIXER OPEN
——
5 - 25
MIXER CLOSED
——
20 °C - 110 °C
MAX FLOW TEMPERATURE
80 °C
10 °C - 110 °C
MIN FLOW TEMPERATURE
30 °C
(-15)°C - (5)°C
FROST PROTECTION TEMP
0 °C
0:00 - 24:00
OUTSIDE TEMP DELAY
0.00
00K - 50K
HEATING SLOPE DISTANCE
5 °C
00 - 01 (OFF / ON)
B-HEAT SINK
01
Exit level using
RETURN
01 - 06
SEQUENCE MODE
01
Summary of Contents for XC-K oil 100
Page 63: ...63 ...