29
Installation instructions
ENGLISH
( * )
If the storage tank temperature sensor is connected, dhW ser-
vice is automatically activated on boiler power supply.
Parameter (803)
srv
(is automatically updated).
( ** )
relay contact that closes when in alarm mode
( *** )
Shc optional
The system can power only one Shc module.
If you need to have more than one Shc module, they must be
placed externally in a dedicated electrical panel and
powered with their own power supply unit.
connections for:
Y2 Bcm
modbus Bcm
A
B
1
2
remote boiler control
A (1) data connection
B (2) data connection
P. mod
4 - 5
modulating heating pump
Se
6 - 7
external sensor
- / +
6 - 7
0 / 10 V signal contact
Stemp Acc
( * )
6 - 8
Storage Tank Temperature
Sensor
fl
fl - 10
Flow switch (remove jumper)
InAIl
11-12
Safety devices
(remove jumper)
TA
TA - 9
room thermostat / clock
remove jumper
6
7
8
9
10
11
12
F L
T A
Y2- BCM
1
2
3
4
5
FL
SE
TA
Alarm
signal
+
(+
)
0
-1
0
V
(-)
G
N
D
P.
Mod.
C.P.M.
Alim.
230V
Stemp.
ACC
P.
Coll.
P.
CH
P. Car.
DHW
1
2
3
Y5
0 1
2
3
4
5
6
7
8
9
2
3
4
Y3
1
2
3
4
1
5
6
7
Y4
5
4
3
2
1
7
6
5
8
4
3
2
Y2
Y1
1
J 1
P
SHC
Modbus
INAIL
SAFE
IN
P
U
T
0-10V
1
Y3- BCM
Y2-HSCP/UFLY
5
6
8
4
3
Y1- BMM1
4
3
2
1
Y4- BCM
2
3
INAIL
Modbus
BCM
Ufly
Y4 - Bcm
Alarm signal
(**)
3 - 4
Alarm / signal contact
(no potential-free contact)
P. coll.
1 - 2
manifold pump (primary loop)
Y3 - Bcm
P. ch
1 - 3
heating circuit pump
P. car dhW
1 - 2
Storage Tank loading Pump
Y2 - uflY
Modbus Ufly
A
B
5
6
remote Temperature control
A (5) data connection
B (6) data connection
Y1 Bmm1
Shc
(***)
8 - 4 - 3
optional multifunction module
(to be inserted in the box cover)
The
BCM
and
shC
relay contacts support
pumps with
max. 4A absorption.
modbus Bcm
can be used for control from building automation,
can also be connected
with Modbus Ufly to have a single bus.
Summary of Contents for MODULEX EXT Series
Page 1: ...e n G l I S h INsTALLATION AND MAINTENANCE INsTRUCTIONs 348 440 550 660 770 900 moduleX eXT...
Page 25: ...25 Installation instructions E N G L I S H PAGE LEF T INTEN TION ALL Y BLANK...
Page 30: ...30 PAGE LEF T INTEN TION ALL Y BLANK...
Page 34: ...34 ON ON OFF 10V ON 10V Wilo Stratos modulating pump setting ext input enabling 0 10 V...
Page 51: ...51 Installation instructions E N G L I S H PAGE LEF T INTEN TION ALL Y BLANK...