8
1.7 - wATER TREATMENT
The treatment of the supply water
allows to prevent inconveniences
and maintain the functionality and
efficiency of the generator over time.
The ideal water pH in heating systems
must be within:
To minimise corrosion, it is crucial to
use a corrosion inhibitor; in order for
it to work properly, the metal surfac
-
es must be clean.
(see system protection ACCEssO-
RIEs sect. in domestic price list)
ATTENTION (*) see general warnings
1.1:
The heating only models are NOT
suitable for the production of water
for human consumption according
to Ministerial Decree D.M. 174/2004.
ATTENTION!
ANY DAMAGE TO THE BOILER
CAUsED BY THE FORMATION OF
FOULING OR BY CORROsIvE wA-
TER wILL NOT BE COvERED BY THE
wARRANTY.
1.8 - BOILER ANTIFREEZE
PROTECTION
To activate the antifreeze function, position
the two knobs as shown in the figure.
This protection can intervene only if
the electricity and gas supplies are
connected.
If one of the two is not available and upon
reset
11 (sR)
a temperature of < 2 °C is
detected, the appliance will behave as
described in tab.
pos 2.
The heating system can be protected
effectively from frost by using antifreeze
products with inhibitor for heating
systems.
Do not use car engine antifreeze
products as they could damage the
water gaskets.
VALUE
MIN
MAX
PH
6.5
8
Hardness [°fr]
9
15
NOTE!
Further details in the section
‘‘Technical Information’’ on the boiler
page of the www.unicalag.it website
P
O
s
ANTIFREEZE FUNCTION
Power supplies
11 - sR
(*)
Status
function
antifreeze
Actions
Electric
Gas
1
ON
ON
< 6 °C
ON
- Burner and Pump ON until T > 14°C
2
ON
OFF
< 2 °C
ON
Only when both the power supplies are ON:
- Burner and Pump OFF until T > 5°C
- When T > 5°C then Burner and Pump
ON until T > 14°C.
OFF
ON
OFF
OFF
(*) Sensor 11 par. 2.2