35
ENGLISH
Installation Instructions
BCM Parameters
Code Symbol
Description
Unit
Min.
Max.
Imp. Fab.
803
Srv
Enabled Services
16
27
19
483
rP
Gen: Temp. Max Differential
°K
0,0
50,0
0
34
HY
Burner Hysteresis
°K
5,0
20,0
5,0
31
HL
CH#1: Minimum Set-point
°C
20,0
40.0
35,0
39
HH
CH#1: Maximum Set-point
°C
45,0
85.0
80,0
799
AC
Input 0/10V
0
3
1
376
DI1
Programmable Input #1
0
2
0
322
Po
Pump: Post-circulation
min.
1
10
5
341
PL
Pump: Minimum Control
V
0
10
3
313
Pr
Pump: Maximum Control
V
0
10
10
792
CHP
CH: Mx. Modulation
%
0
100
100
611
POT
Gen: Err. Max. Parallel
°K
0
30
5
612
POL
Gen: Mod. Max. Parallel
%
0
100
0
650
dL
DHW: Minimum Set-point
°C
25,0
45,0
35,0
385
dH
DHW: Maximum Set-point
50,0
65,0
65,0
360
dt
Storage Tank Adjustment
0
15
0
656
drT
DHW: Temp. Requested Differential
°K
-20
20
4
657
drH
DHW: Requested Temp. Hysteresis
°K
1
20
8
310
DpT
DHW Pump: Postcirc.
sec.
5
600
60
660
dbT
DHW: Temp. Maximum Boiler
°C
50,0
85,0
75,0
48
ChSet
CH#1: Set-point
°C
20,0
85,0
85,0
64
ChPO1
CH#1: Parallel Supply
0
1
0
346
FL
Minimum Modulation
%
0
100,0
25,0
600
mB
Burners: Min. Inserted
1
8
1
616
BSt
Gen: Insertion Time
sec.
30
900
120
613
BRt
Gen: Removal Time
sec.
30
900
120
336
HS
Temperature Gradient
°C/min
1
30
5
353
HP
CH PID: Proportional
°K
0
50
25
354
HI
CH PID: Integrative
°K
0
50
12
478
Hd
CH PID: Derivative
°K
0
50
0
816
MI
Modbus Address
1
127
1
817
MT
Modbus Time-out
sec.
0
240
30
896
TU
°Fahrenheit
0
1
0
309
St
Application Code
0
1
1
368
VA1
Programmable Relay #1
0
1
0
369
VA2
Programmable Relay #2
0
1
1
771
PS
Water Pressure Sensor
0
1
0
768
LG
Min. Gas Pressure Sensor
0
1
1
793
COC
Chimney Obstruction Sensor
0
2
1
622
FS
Minimum Flow Sensor
0
1
3