P/N:110401104451X

5.2

Test leads connection

Make sure all the test leads are firmly connected to the Tester input terminals;

Poor connection will affect the measuring accuracy.

6. Making Measurements

Warning

The voltage up to 50Vac will be present between E and C input terminals 

during earth ground resistance measurement. To avoid any electric shock, 

do not touch exposed metal part of test leads and auxiliary earth stakes.

6.1

Precision Measurement

 (with use of standard test leads):

    

a

.  place 2 ground stakes deep into the soil.  Earth electrode(E), probe(P) and

             auxiliary earth (C) should be in a straight line and 5-10m apart from each other. 

            See Figure 2 for the connection.

            ( Caution: ensure the ground stakes in the damp soil. If the soil is too dry, it

            need to fill-in sufficient water. Stony or sandy soils also needs to be dampened 

before test. If the testing site is covered with concrete in the city area, which 

makes it impossible to insert the ground stakes, you can place 25cm X 25 cm 

two steel plates (or the existing ground stakes) horizontally on concrete 

surface, and cover with the towel dampened sufficiently with water, then 

measuring electrodes are produced and under general circumstances, the 

measurement can begin now.)

Figure2

C: auxiliary electrode     P: potential electrode     E: earth electrode

Auxiliary

Earth stakes

Earthed Electrode

Under Test

Red

Yellow

Green

m

m

 b.  Measuring Earth Voltage:

1)  Set the rotary switch to EARTH VOLTAGE, LCD shows the Tester enters into 

     earth voltage test status.

2)  Insert test leads into V and E terminals and then connect them to tested points.

     (Do not make any connection to other terminals)

3)  The measured earth voltage shows on LCD. If the measured voltage is 

10V,  

     please switch off all related electrical equipments and wait until this voltage 

     decreases before you makes any earth resistance measurement, otherwise it 

     may affect the accuracy of earth resistance measurement.

Warning:

Only V and E input terminals are used for earth voltage measurement, do not 

make any connection to C and P terminals. Otherwise, it will cause danger and 

damage the Tester.

c.   Measuring Earth Ground Resistance:

1)  Set the rotary switch to earth ground resistance 2000Ωrange.

2)  Press “TEST” button, the button will be illuminated, indicating the instrument is 

     under measurement status. And LCD shows the measured earth resistance value. 

     If measured earth resistance:

200Ω, turn the rotary switch to 200Ω range;

                                          

20Ω, turn the rotary switch to 20Ω range;

     Or you can select earth resistance range in an order you like, however, to obtain 

     accurate value, make sure you have selected the best range for your measurement. 

         Caution: 

●  If C or E input terminal is not well contacted, or auxiliary earth resistance or 

    measured earth ground resistance is too large or input terminal are opened 

    ( > 14kΩ at 20Ω range), the LCD will show “- - - -Ω”. Please check if the test 

    leads are firmly connected or the soil is too dry or the auxiliary earth stake has 

    been properly inserted into the earth. 

●  When measured earth resistance is out of range, and it is

14kΩ at 20Ω range 

    or 

26kΩ at 200Ω range or 

78kΩ at 2000Ω range, LCD will show “OL” icon 

    (Overloaded).

●  The reading may be affected if auxiliary stakes are bent or in contact with other 

    objects. So please clean the earth stakes before connecting the test leads, 

    otherwise it may cause deviations to the readings if the auxiliary stake has a large 

    resistance.

d.   Auto Power Off:

 The Tester will automatically switch off to conserve the energy 

      after the buttons and rotary switch keep inactive for 10 minutes (except under 

      earth resistance test status.)

e.  Backlight:

 When making measurements in dimly lighted sites, press “Light

     /Load” button to turn on the backlight, and its icon indicates on LCD accordingly. 

     Press it again to turn off the backlight.

f.   Data Hold:

 During the measurement, gently press “Hold/Save” to freeze the 

     measured value, indicated by HOLD icon on LCD, press the button again to 

     disable the function.

     3. 

Clear Saved Data

        Press and old "Hold/Save"button and "Light/Load"button simultaneously, then 

        switch-on the Tester, LCD display will show"C L .",

        Meanwhile, all the data in the memory will be deleted no matter whether the 

        memory is full or not.

6.2  Simple Measurement (with use of simple test leads):

This method is applied when auxiliary stake is impossible to use, which use an 

exposed object with low earth resistance as one electrode, such as metal water 

slot, pipe, common earth of power supply wiring, earth ground terminal of buildings, 

etc.(using E and P&C terminals).See Figure 3 for wire connection:

Figure 3

Primary

Side

Red

Green

Secondary

Side

Supply Transformer

Reference Earthed

Electrode

Earthed Electrode

Under Test

r

When using this method, P and C have already been connected together.

Danger

Please take extreme caution about the electric shock when using earth 

ground terminal of commercial power system as a reference test point.

7. Maintenance & Repair

7.1

Maintenance

7.1.1

 Replacing the Battery (See Figure 4)

         Please replace the battery timely when low battery indicator shows. Follow 

         the steps as below:

Figure 4

g.   Data Storage:

1.   Save Data:

 Long press “Hold/Save” button for 2seconds to enable Data Save 

      function and meanwhile save the data accordingly, then gently press the button 

      again to save the second set of data, circulate so on and so forth. To cancel the 

      function, long press “Hold/Save” for 2s to exit.

2.   View Data:

 Long press “Light/Load” for 2s to recall NO.01 data, then gently 

      press the button to recall NO.02 data…. up to 20sets of data. To return to 

      previous set, gently press “Hold/Save” button.(Under this status, “Hold/Save” 

     a. switch-off the Tester and remove all the test leads.

     b. release the screw in bottom part,and open battery compartment.

     c. Replacing all old battery (6) with new battery.

     d. After replacing the battery, rejoin the battery compartment and firmly screw.

         Remove all the batteries if the Tester do not use for a long time so as to

         avoid the leakage and corrosion in the battery compartment.

  7.1.2 Cleaning the Tester

           Soft cloth and mild detergent should be used to clean the surface of the Tester,

           no solvent or alcoholic is allowed for it may damage the display.

  7.1.3 Must be avoiding moisture.

7.2

 Repair

7.2.1 Contact our after-sales service department or agents when the following 

         incidents happen:

           a. The Tester is being damage.

           b. LCD display abnormally.

           c. Unreasonable deviation when in normal use.

         d. Buttons do not function properly.

7.2.2 when the Tester needs repair, please have it serviced by qualified 

         professional personnel or authorized service center.

This operating manual is subject to change without notice.

**END**