INSTRUCTIONS FOR AUTOMATIC TEST
(SELF DIAGNOSTICS /SELF-TEST FUNCTION OF EMERGENCY LIGHTING)
Battery charging time: 24h
1 ) Install the lighting fixture according to the installation manual
2 ) After switching on the unit, it automatically carries out the following self-test:
-
24 hours after the installation
Performing a 3 hours long term test
-
Each 10 seconds:
Performing a quick test to check if the battery is connected
-
Weekly:
Performing a 5s function test, check for battery interruption, charger error, lamp failure or led driver failure
-
Yearly:
Performing a 3 hours long term test
All test functions are preset at the factory and do not have to be adjusted on site. If needed all the parameters can be adjusted through the DALI line.
3 ) Meaning of the two colors LED status displays
Green
lights up
ready/ normal operation
flashes
Test mode
Red
Maintenance required
Green
Fast flashing,
0.1 second On / 0.1 second Off
Function test
Green
Slow flashing
1 second On / 1 second Off
Long term test 3h
Green
Double pulsing
Inhibit Mode, can be activate through the DALI line. In this mode the unit is disabled for DC
operation. Useful if the unit is temporary not used for emergency when the power cut off but
the tests are maintained and the battery remains used. (good for the battery)
Red
Lights up
Circuit board failure Charger failure, short circuit
Red
Slow flashing
1 second On / 1 second Off
Battery failure
No LED
No LED
In battery operation, DC mode
/
Flashing red then green
During DALI Addressing process
Technische Änderungen vorbehalten / Les détails techniques sont sujet à des changements.
Technical Details are subject to change.