UltraGlow
®
G36D Zero Clearance Direct Vent Gas Fireplace
17
INSTALLATION
The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, with
Rigid
Pipe
vent systems for Propane and Natural Gas, as per the diagram 3.
The shaded area in the diagram 3 shows all allowable combinations of straight
vertical and offset to vertical terminations with
Rigid Pipe
vent systems for
Propane and Natural Gas. Maximum two 45
o
elbows allowed.
• Vent must be supported at offsets
• Firestops are required at each fl oor level and whenever passing
through a wall.
• Maintain clearances to combustibles as listed in the "Clearances"
section.
Diagram 3