2

110498

Wet

Module

Fig. 1

Mounting

Bolts

Open Windows To Exhaust Air

An often misunderstood concept of evaporative cooling is the amount
of air that should be exhausted.  How much should you open your
windows?  The fact is that most people do not open their windows
enough.  The following two methods will help you determine the amount
to open your windows.

First Method

You should allow an opening of at least 2 square feet (288 square
inches) for each 1000 CFM rating of your unit.  

Example:

  At 3320

CFM, model ADA 50 (1/2 hp) requires 6.6 square feet (950 square
inches) of opening  (3320/1000 * 2 = 6.6).  Multiply the number of
windows by window width in inches and divide this into the number of
square inches required for your size unit.  This will give you the height
to open windows.  In this example, four 36 inch wide windows should
be opened 6.6 inches each.

Champion Air Balancing Method

1. Take a piece of tissue paper and cut it lengthwise into 3 equal strips.
2. Turn your cooler on high cool.
3. Open one window at least six inches wide in each room that you

want to cool.

4. Take the piece of tissue paper and put it up against the screen of the

open window furthest from the cooler discharge opening.  Let go of
it.  It will do one of three things.

IF

It falls down.

THEN

CLOSE all of the windows one inch and try step 4 again.

IF

It plasters itself to the screen.

THEN

OPEN all of the windows one inch and try step 4 again.

IF

It stays on the screen lightly.

THEN

PERFECT.  You are done.  Enjoy your cooler.

NOTES:

• When switching to low cool, you must rebalance your home.  Repeat

step 4.

• Once you balance your home you can cool some areas more than

others by opening those windows more and closing the others by the
same amount.  Repeat step 4 to make sure your home is still air
balanced.

Motor
Clips

Yoke

Adjustable
Yoke

Fig. 2

Blower

Housing

Motor
Pulley

Blower
Pulley

Fig. 3

Screws

Fig. 4

Junction
Box

CAUTION:

  Do not screw or drill within

5 inches of the bottom of the wet module.
You could puncture the reservoir.

NOTE:

  You can separate the wet module

from the blower module by removing the 4
bolts (2 bolts in ADA35 and ASA35) from
the wet module side (Fig. 1)

Motor Installation

Install motor cord.

  For

typical 120V installation,
connect motor cord to mo-
tor using the following color
code: Black - Hi, Red - Low,
White - Com., Green -
Ground.

Mount motor.  

Install

blower motor in the motor
mount yokes, adjusting the yoke
if necessary.  Fasten with the pro-
vided mounting clips (see Fig. 2).

NOTE:

  Adjustable yoke will have

to be reversed for 1 H.P. motors.

Install pulley.

  Install the adjust-

able motor pulley so that it aligns
with the blower drive pulley (see
Fig. 3) and tighten set screw.

Electrical Installation

WARNING:

 

 Disconnect all electrical service that will be

used for this unit before you begin the installation.

Remove junction box.

  The

electrical junction box is lo-
cated in the upper inside of
the left center post.  Remove
the two screws and pull box
out from panel for access to
plug wiring (Fig. 4).

Hook up electrical.

  Electri-

cal hook up should be done by a qualified electrician, so that all
electrical wiring will conform to your local standards.  This unit is
suppled with a 120V pump.  For 240V pump operation, a 240V
pump must be purchased.  The fan and pump receptacles will
support both 120V and 240V installations.  See the wiring dia-
grams for 120V and 240V installations on the following page.

IMPORTANT:

  When a single speed motor is used, do not use the

red lead on the receptacle and motor plug wiring.  Tape off end of
both of the red leads.

CAUTION:

  Pump receptacle is for grounded evaporative

cooler pump only.  Do not plug anything else into receptacle.

WARNING:

  Make sure that cooler cabinet is properly

grounded to a suitable ground connection for maximum safety.

Operation

To eliminate the delivery of hot air when starting the cooler, start the
pump only for the first few minutes, then turn on the blower motor.

These coolers may be used without water for ventilation purposes.
When outside air is cool (for example, at night) or when humidity is
high the water pump can be turned off.

A cooler can also be installed with a thermostat and attic exhaust
dampers to provide completely automatic operation.

Cooler Installation

CAUTION:

  Make sure that the mounting surface is strong

enough to support the operating weight of the cooler when in
use.  (For operating weight, see Specification Table.)

CAUTION:

  Never plug in cooler until installation is com-

plete and unit has been tested for rigidity.

Water Connection

Install overflow assembly.

  Remove nut and place nipple through

the hole in the pan, with the rubber washer between the pan and the
head of the drain nipple (Fig. 6).  Screw on  nut and draw up tight
against bottom of pan.  Insert overflow pipe in nipple to retain

Summary of Contents for ADA35

Page 1: ...r 110498 3 05 www championcooler com Table Of Contents Safety Instructions 1 Operation 2 Installation Instructions 2 3 ElectricalWiring Diagram 3 Maintenance Section 3 4 Troubleshooting 4 Warranty 5 Specification Tables Tablas de Especificaciones 5 Parts List ADA35 ASA35 6 7 Parts List ADA50 ADA50 12 ADA70 ADA70 12 8 9 Parts List ASA50 ASA50 12 ASA70 ASA70 12 10 11 Parts List AUA50 AUA70 AUA50 12 ...

Page 2: ...ck Hi Red Low White Com Green Ground Mount motor Install blower motor in the motor mount yokes adjusting the yoke if necessary Fasten with the pro vided mounting clips see Fig 2 NOTE Adjustable yoke will have to be reversed for 1 H P motors Install pulley Install the adjust able motor pulley so that it aligns with the blower drive pulley see Fig 3 and tighten set screw Electrical Installation WARN...

Page 3: ...rvoir Tighten screw 6 Slide float shield 8 up over float body 5 until it snaps into place working inside This should be done for your safety Adjust pulley to a larger diameter and readjust belt tension plug motor in install inspection panels and retest amperage draw Repeat this pro cess until correct amperage draw is attained Increasing motor pulley diam eter increases amperage draw Decreasing mot...

Page 4: ...ined you can get many years of efficient and satisfactory ser vice from your cooler In the event additional information is desired your dealer will be more than glad to assist you in every possible way Problem Possible Cause Remedy Failureto start or no airdelivery Inadequate airdelivery withcooler running Water drainingonto roof Musty or unpleasant odor 1 No electrical power to unit Fuseblown Cir...

Page 5: ...nty applies to original purchaser only Motor Specifications Especificaciones Del Motor General Specifications Especificaciones Generales Models Modelos Weight lbs Peso libras Cabinet Dimensions in Dimensiones De La Caja pulgadas Duct Opening in Abertura De Ducto pulgadas Dry Seco Operating Lleno Height Altura Width Anchura Depth Profundidad Width Anchura Height Altura ADA35 ASA35 120 169 22 9 16 3...

Page 6: ...ibutor Bracket Right Soporte Para El Distribuidor De Agua Derecha 222004 005 222004 005 24A Water Distributor Bracket Left Soporte Para El Distribuidor De Agua Izquierda 222004 003 222004 003 25 Evaporative Media Medio Evaporativo 110103 110103 26 Support Media Soporte Para El Medio Evaporativo 222130 027 222130 027 27 Water Reservoir Bandeja Acumuladora De Agua 281030 281030 28 Pump Mount Montura...

Page 7: ...498 Replacement Parts Piezas De Repuesto ADA35 ASA35 20 4 35 38 37 25 28 30 31 32 29 27 16 6 ADA35 23 24 21 40 10 26 22 39 34 14 13 11 12 24A 8 3 ASA35 6 ASA35 33 19 5 ADA35 3 ADA35 17 18 15 9 1 7 2 5 ASA35 ...

Page 8: ...ver Flow Assembly Montaje De Desagüe 3OA 1 3OA 1 3OA 1 3OA 1 28 Float Valve Flotador FL BK FL BK FL BK FL BK 29 Pump Assembly Bomba C60P 120 C60P 120 C60P 120 C60P 120 30 Tube Water Delivery Tubo De Agua 310716 310716 310716 310716 31 Bleed Off Kit Equipo De La Válvula De Desahogo 310586 310586 310586 310586 32 Receptacle Motor Toma De Corriente Del Motor 110393 110393 110393 110393 33 Receptacle ...

Page 9: ... 110498 Replacement Parts Piezas De Repuesto ADA50 ADA50 12 ADA70 ADA70 12 16 23 25 22 2 1 22 15 24 14 19 28 38 33 32 17 37 36 35 18 39 13 10 8 6 5 12 31 30 20 9 7 6 3 11 27 41 4 43 26 42 44 45 46 47 42A ...

Page 10: ...27 Over Flow Assembly Montaje De Desagüe 3OA 1 3OA 1 3OA 1 3OA 1 28 Float Valve Flotador FL BK FL BK FL BK FL BK 29 Pump Assembly Bomba C60P 120 C60P 120 C60P 120 C60P 120 30 Tube Water Delivery Tubo De Agua 310716 310716 310716 310716 31 Bleed Off Kit Equipo De La Válvula De Desahogo 310586 310586 310586 310586 32 Receptacle Motor Toma De Corriente Del Motor 110393 110393 110393 110393 33 Recepta...

Page 11: ... 110498 Replacement Parts Piezas De Repuesto ASA50 ASA50 12 ASA70 ASA70 12 46 22 7 27 45 44 31 30 41 6 9 38 17 32 22 42 26 36 35 3 4 29 20 43 28 19 6 5 12 11 8 10 14 24 15 23 16 25 33 37 39 18 2 1 47 42A ...

Page 12: ... Over Flow Assembly Montaje De Desagüe 3OA 1 3OA 1 3OA 1 3OA 1 28 Float Valve Flotador FL BK FL BK FL BK FL BK 29 Pump Assembly Bomba C60P 120 C60P 120 C60P 120 C60P 120 30 Tube Water Delivery Tubo De Agua 310716 310716 310716 310716 31 Bleed Off Kit Equipo De La Válvula De Desahogo 310586 310586 310586 310586 32 Receptacle Motor Toma De Corriente Del Motor 110393 110393 110393 110393 33 Receptacl...

Page 13: ...sitivo de estado sólido para controlar la velocidad del ventilador Enfriamiento Por Evaporación Este enfriador evaporativo funciona circulando el aire fresco Usted no tiene aire recirculado que esté viciado cargado de humo y olores como ocurre con los sistemas de aire acondicionado a base de refrigeración En cambio se reemplaza el aire completamente cada 2 a 4 minutos abrien do las puertas o las v...

Page 14: ...240V Vea las esquemas del cableado para las instalaciones de 120V y 240V IMPORTANTE Con un motor de una sola velocidad no use la línea roja en el cableado del enchufe y la clavija del motor Envuelva el extremo de ambas líneas rojas con cinta eléctrica PRECAUCIÓN Enchufe una bomba del enfriador evapora tivo solamente y nada más al receptáculo de la bomba ADVERTENCIA Compruebe que la caja del enfria...

Page 15: ...ecte la línea al flotador y apriete la tuerca hasta que no salga agua Afloje el tornillo 6 y ajuste la varilla 7 has ta que el nivel del agua esté a una altura de 1 pulgada por debajo del bor de superior de la bandeja Apriete el tornillo 6 Ponga la pantalla pro tectora del flotador 8 sobre el cuerpo del flotador hasta que se agarre AmperioYTensión De La Correa Esta unidad viene equipada de una pol...

Page 16: ...uando la unidad está funcionando Hace Ruido Motor se apaga y se enciende Enfriamiento inadecuado Demasiada humedad en la casa Olor a encerrado olor desagradable Garantía Limitada La presente garantía se extiende al comprador original de un enfriador evaporativo instalado y utilizado bajo condiciones normales No cubre daños ocurridos por accidente descuido o abuso por parte del propietario No autor...

Reviews: