background image

Outdoor

Condensing Unit

Air Handler

HVAC Supply

Dedicated Ultra-Aire 90 Return to A/C Supply

HVAC Return

Fresh Air Intake 

(Optional)

Motorized

Damper

Indoor

Air Return

Ultra-Aire

Supply

Backdraft

Damper

Recommended Installation

Dedicated Return to HVAC Supply 

•  Create a separate return for the Ultra-Aire SD12  

in a central area of the building.

•  Duct the supply of the Ultra-Aire SD12 to the air  

supply of the HVAC system with a backdraft damper.

•  Supply a line set suitable for use with R410A refrigerant to 

connect the indoor unit to the outdoor unit. The maximum 

allowable length of the line set is 50 feet. Braze the lines 

to the dehumidifier and the condensing unit. 

Outdoor

Condensing

Unit

A/C Return to A/C Supply

Air Handler

HVAC Supply

HVAC Return

Backdraft

Damper

Optional Check Damper

(no HVAC fan needed)

Fresh Air Intake 

(Optional)

Motorized

Damper
Ultra-Aire

Supply

HVAC Return to HVAC Supply

•  Check Damper should be in place between the Return and 

Supply connections of the dehumidifier.

•  If Check Damper is not in place, the HVAC fan must turn on 

when the dehumidifier is in operation.

•  Supply a line set suitable for use with R410A refrigerant to  

connect the indoor unit to the outdoor unit. The maximum  

allowable length of the line set is 50 feet. Braze the lines  

to the dehumidifier and the condensing unit.

Outdoor

Condensing

Unit

Air Handler

HVAC Supply

Dedicated Ultra-Aire 90 Return to A/C Retur

n

HVAC Return

Fresh Air Intake 

(Optional)

Motorized

Damper

Indoor

Air Return

Ultra-Aire

Supply

Dedicated Return to HVAC Return

•  Create a separate return for the Ultra-Aire SD12 in a central 

area of the building.

•  Installing the supply air from the Ultra-Aire SD12 in the  

return of the HVAC system requires the HVAC fan to run 

when the Ultra-Aire SD12 is operating.

•  Supply a line set suitable for use with R410A refrigerant to 

connect the indoor unit to the outdoor unit. The maximum 

allowable length of the line set is 50 feet. Braze the lines  

to the dehumidifier and the condensing unit.

Air Handler

HVAC

Supply

A/C Return to A/C Return

HVAC Return

Fresh Air

Intake

(Optional)

Motorized

Damper

Optional Check Damper

(no HVAC fan needed)

Ultra-Aire

Supply

Outdoor

Condensing

Unit

HVAC Return to HVAC Return

•  Check Damper should be in place between the Return and 

Supply connections of the dehumidifier.

•  If Check Damper is not in place, the HVAC fan must turn on 

when the dehumidifier is in operation.

•  Supply a line set suitable for use with R410A refrigerant to 

connect the indoor unit to the outdoor unit. The maximum 

allowable length of the line set is 50 feet. Braze the lines  

to the dehumidifier and the condensing unit.