Ultra-Aire 98H Installation Instructions

Troubleshooting (Continued)

SERVICE

  Symptom 

Possible Reason 

Troubleshooting Procedure

 

Troubleshooting Procedure for Performance  

Related Issues
This method of diagnosis is used to function 
check the internal components in the dehumidi-
fier. This is to be used when a performance issue 
is suspected.
1.  Set the humidity controller all the way to the 

most humid setting or off position – Did the 
unit shut off?

2.  If yes, turn the fan setting to the ON position – 

does the fan start?

3.  If fan starts, leave in the fan ON position and 

set the humidity all the way to driest setting. 
May have to wait 5 minutes for the compressor 
to start.

4.  Listen for a distinct buzzing/humming sound 

of a compressor starting up – do you hear this 
noise?

5.  If compressor is running and continues to run, 

after about 15 minutes you should feel a slight 
increase in air temperature being discharged 
out of the discharge air side of the unit.

6.  If so, depending on your environmental  

conditions (temp/Rh%), you should see some 
water production out of the hose within  
30 minutes or so. (

Note: If the room  

temperature is 55 degrees or below and/or  

in area of low relative humidity, the  

dehumidifier will produce little to no water.)

7.  Collecting the water removed in a 24 hour period 

will give a measurement of performance. 

 

WARNING!

 

ELECTRICAL SHOCK HAZARD:

  

ELECTRICAL POWER MUST BE PRESENT 

TO PERFORM SOME TESTS. THESE TESTS 

SHOULD BE PERFORMED BY A QUALIFIED 

SERVICE PERSON.

Fan is not running. 
Dehumidification  
or fan is being 
called for.

1.  Loose connection in  

fan circuit.

2.  Obstruction prevents 

fan impeller rotation.

3. Defective fan.
4. Defective fan relay.

Low dehumidification 
capacity (evaporator 
is frosted  
continuously).  
Dehumidification is 
being called for.

1.  Defrost thermostat loose 

or defective.

2. Low refrigerant charge.
3.  Dirty air filter(s) or air flow 

restricted.

4.  Excessively restrictive 

ducting connected to unit.

No ventilation. 
Ventilation is being 
called for.

1.  Loose connection in  

ventilation control circuit.

2.  Loose connection in 

damper power circuit.

3.  Defective fresh air 

damper.

Dehumidifier  
removes some  
water, but not as 
much as expected. 

1.  Air temperature and/or 

humidity have dropped. 

2.  Humidity meter and or 

thermometer used are  
out of calibration.

3.  Unit has entered defrost 

cycle. 

4.  Dirty air filter(s) or air flow 

is restriced. 

5.  Defective defrost  

thermostat. 

6. Low refrigerant charge. 
7.  Air leak such as loose 

cover or ducting leaks. 

8. Defective compressor. 
9. Restrictive ducting. 

Summary of Contents for 98H

Page 1: ...in comfort health and property protection through Dehumidification Fresh Air Ventilation Optional Air Filtration TS 1037 12 17 Rev A P N 4034240 Serial No Install Date Sold by HVAC Installer Please Le...

Page 2: ...ation 13 No Existing Ductwork Installation 14 Recommended Closet Installation 15 Alternative Closet Installations 16 Fresh Air Ventilation 17 Determine Ventilation Requirements 18 Controls 19 Wiring C...

Page 3: ...LATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN DEHUMIDIFIER IS HEAVY HANDLE WITH CARE AND FOLLOW INSTALLATION INSTR...

Page 4: ...ons 6 Round Inlet 10 Round Inlet 10 Round Outlet Air Filter MERV 13 Mini Pleat Efficiency 90 ASHRAE Dust Spot Size 14 x 17 5 x 1 75 Optional Air Filters MERV 11 Mini Pleat Efficiency 65 ASHRAE Dust Sp...

Page 5: ...Insulated Duct 25 4020656 6 Inlet Hood 4024375 10 Gravity Damper 4026969 10 Flex Duct 25 4022126 10 Flex Insulated Duct 25 Items Included in Box Ultra Aire 98H Dehumidifier Ultra Aire 98H Installation...

Page 6: ...ficient clearance for filter removal and to prevent airflow obstruction Electrical service access will require the removal of a side panel Allow sufficient clearance on a side of the unit Locate the d...

Page 7: ...let A B C A B C Air Flow Rear View Front View A B Fresh Air Ventilation Duct Fresh air ventilation is optional A 6 diameter duct is attached to the unit The 6 duct should be capped if fresh air is not...

Page 8: ...22 gauge thermostat wire ELECTRICAL REQUIREMENTS CAUTION DO NOT ALLOW THE 24V TERMINAL TO CONTACT THE COM DMPR TERMINALS ON THE ULTRA AIRE 98H OR DAMAGE TO THE TRANSFORMER WILL RESULT Electrical Preca...

Page 9: ...densate Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch The pump also contains a safety float switch The white lead...

Page 10: ...rigid ductwork in the structure Use a minimum 10 diameter round or equivalent rectangular duct for total duct lengths of up to 25 Use a minimum 12 diameter round or equivalent rectangular duct for lo...

Page 11: ...ing a dedicated return to the Ultra Aire 98H it is possible to select one to disconnect from the existing HVAC system and use it for the dedicated Ultra Aire 98H return Select a return from a central...

Page 12: ...tra Aire Return to HVAC Supply Installation is not possible there are several alternative installation options available DO NOT locate return in a bathroom or kitchen Control should be located remotel...

Page 13: ...location HVAC systems should be in close proximity for optimal air flow For multiple systems contact Technical Support at 800 533 7533 DUCTING TO HVAC SYSTEMS Recommended Multiple HVAC Systems Install...

Page 14: ...ure to utilize multiple rooms to allow air inside the structure to properly circulate Proper air distribution is important to ensure even humidity control and heat distribution throughout the structur...

Page 15: ...re 98H to provide fresh air ventilation optional Control should be located remotely from the dehumidifier and placed in a central location Where outlet space is restricted the outlet duct collar is op...

Page 16: ...tral Return to HVAC Return Attach outlet duct with a vertical flow through so air is not discharged into wall or other obstruction see Page 7 for Vertical Flow Through The HVAC system will naturally p...

Page 17: ...amper is used a digital control is required It may be necessary to use 8 duct work if additional fresh air is required In cold climates or at times when the dew point is low ventilation can be used to...

Page 18: ...X 0 03 5 X 7 5 91 5 CFM Record the required CFM ____________ FRESH AIR VENTILATION Determine Ventilation Requirements The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 2016 Use one o...

Page 19: ...t breaker without correcting the electrical short may result in transformer damage Be sure to check the electrical schematic in this manual or inside the access panel of the Ultra Aire 98H before maki...

Page 20: ...mpressor Control DMPR 24VAC Power Transformer Neutral Side Spare Terminal Open Terminal Block Control Operation Unit ON Make contact between 24V and DEHU terminals Unit OFF Make contact between 24V an...

Page 21: ...1 Pull back slide latch to swing filter door open Step 2 Remove the filter by gently pulling it straight out of the unit Insert new filter by gently pushing it straight into the unit Make sure the AI...

Page 22: ...ag Filter Nonsupported Legionella microfine fiberglass or 11 60 65 95 Humidifier Dust Better Commercial Buildings synthetic media 12 36 in deep 6 12 pockets Lead Dust 10 50 55 95 Milled Flour Box Filt...

Page 23: ...n the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type SERVICE Service Parts List Item Part No Description 1...

Page 24: ...er only the fan should run Disconnect the terminals 8 Connect the 24V and DEHU terminals together fan and compressor should run Disconnect the terminals 9 If this test works then the field control wir...

Page 25: ...es or below and or in area of low relative humidity the dehumidifier will produce little to no water 7 Collecting the water removed in a 24 hour period will give a measurement of performance WARNING E...

Page 26: ...rol wiring 3 Check wire connections at control and unit 4 Reset circuit breaker button on dehumidifier WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS THESE TEST...

Page 27: ...ts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilit...

Page 28: ...800 533 7533 www Ultra Aire com...

Reviews: