2.2 Wiring

 WARNING!

 

DO NOT ALLOW THE YELLOW 

WIRE FROM THE ULTRA-AIRE DEHUMIDIFIER TO CONTACT 
THE RED OR WHITE WIRES FROM THE ULTRA-AIRE 
DEHUMIDIFIER, DAMAGE TO THE 24-VOLT TRANSFORMER 
WILL RESULT.

 WARNING!

 

THE REMOTE CONTROL OF THE 

ULTRA-AIRE DEHUMIDIFIER OPERATES ON A LOW VOLTAGE 
CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE 
CONNECTED TO A HIGH VOLTAGE CIRCUIT.

 WARNING!

 

UNPLUG THE ULTRA-AIRE 

DEHUMIDIFIER BEFORE WIRING THE DEH 3000R.

The installer must supply all field wiring, including the 
wiring between the Ultra-Aire dehumidifier and the DEH 
3000R. Some of the control wires leaving the Ultra-Aire may 
not be used in some control situations and should be left 
disconnected with wire nuts taped onto the stripped ends.

Be sure to consult the electrical schematic in this manual or 
the internal electrical box of the Ultra-Aire dehumidifier before 
making any control connections.

 WARNING!

 

ONLY CONNECT THE WHITE WIRE 

TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH 
AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER 
DAMAGE MAY RESULT.

The White wire controls the optional motorized damper 
that can be installed into a fresh air duct. This damper 
provides the ability to control fresh air ventilation using 
the ventilation timer function of the DEH 3000R and 
the terminal labeled 

“DMP”

 on the DEH 3000R (See 

Section 3.8). Leave the 

“DMP”

 terminal unused if a 

motorized damper is not used, and cap off the White 
wire from the Ultra-Aire dehumidifier.

Standard wire colors for thermostats are as follows:
Description 

Color 

Terminal code

24VAC  Red R
Call for Heat 

White 

W or W1

Force Fan On 

Green 

G

Compressor 
Call for Cooling 

Yellow 

Y or Y1

2.3 Auxiliary relay operation

It may be desirable to coordinate fan operation of the central 
heating/cooling system with dehumidifier fan operation. The 
DEH 3000R contains a relay that provides this ability. 

The relay terminals labeled NC, COM and NO operate according 
to the following chart:

FAN 

COM to NO 

 COM to NC

ON 

CONNECTED 

 OPEN

OFF  

OPEN 

CONNECTED

Common uses (assuming standard thermostat wiring colors as 
noted):

Lock-out the A/C during dehumidifier fan operation

This will turn off the A/C whenever the dehumidifier fan runs.

DEH 3000R Dehumidifier & Ventilation System Controller

 Installation, Operation & Service Manual

NO

COM

NC

Summary of Contents for DEH 3000R

Page 1: ...E LEAVE MANUAL FOR HOMEOWNER Dehumidifier Ventilation System Controller 2008 Therma Stor LLC Manual P N TS 506d 12 12 4201 Lien Rd Madison WI 53704 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com DEH 3000R DEH 3000R Part No 4028407 ...

Page 2: ... F 2 Size 4 95 L x 1 06 W x 4 19 H 2 Installation Install the DEH 3000R remote sensor in a central area of the structure where it will sense the relative humidity of the structure accurately Do not install the remote sensor where it may not accurately sense the relative humidity such as near HVAC supply registers near exterior doors and windows or near a pool or spa Install in accordance with all ...

Page 3: ...T The White wire controls the optional motorized damper that can be installed into a fresh air duct This damper provides the ability to control fresh air ventilation using the ventilation timer function of the DEH 3000R and the terminal labeled DMP on the DEH 3000R See Section 3 8 Leave the DMP terminal unused if a motorized damper is not used and cap off the White wire from the Ultra Aire dehumid...

Page 4: ...n be identified as the wire from the A C transformer that reads 0 volts between it and the Yellow air conditioning call for cooling wire The incorrect wire will give a 20 to 28 volt reading 2 Another Yellow wire must be added to the thermostat Yellow terminal and run to the ON D sensor terminal on the DEH 3000R Deactivate dehumidification when the air conditioner is running A voltmeter is required...

Page 5: ...it again to switch the fan to the ON setting c Confirm that the Ultra Aire fan is ON Ultra Aire compressor must be OFF Ventilation damper if used should be CLOSED 6 Verify optional VENT operation if electric damper is installed a Press and hold the FAN button until ON flashes on the display b Release the FAN button then press it again to switch fan operation to AUTO c Press and hold the VENT butto...

Page 6: ... A flashing O before the SET POINT VENT OR FAN indicates the unit is in wait mode 3 2 Setting During the set up process if you make a mistake simply continue You can always go back to adjust the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to the normal display screen allowing you to proceed to the next ste...

Page 7: ...d 3 7 Fan Setting and Operation Use the FAN button to change the fan operation There are 2 choices for fan operation ON or AUTO The factory preset is AUTO ON The fan in the Ultra Aire dehumidifier will run continuously This does not affect either the dehumidification or ventilation functions of the system The system may or may not be ventilating or dehumidifying while the fan is running This setti...

Page 8: ...the display Release the button 2 Press the VENT button again to switch between OPEN and CLOSED 3 Leave the control alone for 10 seconds and your settings will be saved 3 9 Damper Operation and Ventilation Programmed Ventilation This example shows the system in program mode denoted by the schedule 15 minutes on 5 minutes off and the word RUN in the lower right corner of the display The DEH 3000R wi...

Page 9: ... schedule Repeat the steps listed above for this and the SAT SUN day and night schedules When you have finished programming your schedule either the 7 day version or the weekday weekend split version use the down RH button to highlight the EXIT option and then press PROGRAM ENTER to select it Running the Ventilation Program Press and hold the PROGRAM ENTER button until the PROGRAM screen appears U...

Page 10: ...e may limit sensor distance Thicker gauges will not work with splice connectors provided Avoid routing parallel to high voltage wiring Maintain a distance of 2 ft or more from high voltage lines 2 Sensor connection The sensor can be mounted to a wall or ceiling surface Ideal sensor location is 5 ft above the floor Wires should exit through a diameter hole in the mounting surface at the mounting lo...

Page 11: ...come effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the applicable warranty period Therma Stor shall have no obligation hereunder with respect to any claim received by Therma...

Page 12: ...ct to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2007 Therma Stor LLC All rights reserved DEH 3000R Dehumidifier Ventilation System Controller Installation Operation Service Manual ...

Reviews: