S9110-32X Hardware Installation Guide | 4
•
Cooling: The S9110-32X has two options for airflow direction. There is a back-to-front
option (Figure 3. Left) and a front-to-back option (Figure 3. Right). Make sure the
equipment on the same rack have the same airflow direction.
Back-to-Front Airflow
Front-to-Back Airflow
Figure 3.
Figure 4.
Preparation Check List
Task
Check
Date
Power voltage and electric current requirement
DC version
: -40 to -75V DC, 28A maximum x2 or;
AC version:
100 to 240V, 10A maximum x2
Installation spacing requirement
:
S9110-32X spacing requires a height of 1RU (1.72
”/4.5cm),
a width
of 19
” (48cm)
and a depth of 18.9 inches (4.38cm)
Thermal requirement
S9110-32X working temperature using back to front airflow is 0 to
40°C (32°F to 104°F), for font to back airflow it is 0°C to 45°C (32°F
to 113°F)
Installation tools required
#2 Phillips Screwdriver, 6-AWG wire stripper, and crimping tool
Accessories required
PC with terminal emulation software, console cable, 10-AWG wire
with ring terminal for power, 6-AWG wire for grounding
Rear wall clearance =
6”