S6301-56ST Hardware Installation Guide | 4
•
Cooling: The S6301-56ST has two options for airflow direction. There is a back-to-front
option (Figure 3. Left) and a front-to-back option (Figure 3. Right). Make sure the
equipment on the same rack have the same airflow direction.
Back-to-Front Airflow
Front-to-Back Airflow
Figure 3.
Figure 4.
Preparation Check List
Task
Check
Date
Power voltage and electric current requirement
DC version
: -36 to -72V DC, 6A maximum x2 or;
AC version:
100 to 240V, 3A maximum x2
Installation spacing requirement
:
S6301-56ST spacing requires a height of 1RU (1.72
”/4.5cm),
a width
of 19
” (48cm)
and a depth of 17.32 inches (44cm)
Thermal requirement
S6301-56ST working temperature is 0°C to 45°C (32°F to 113°F)
Installation tools required
#2 Phillips Screwdriver, 6-AWG wire stripper, and crimping tool
Accessories required
PC with terminal emulation software, console cable, 18-AWG wire
with ring terminal for power, 6-AWG wire for grounding
Rear wall clearance = 6”