All the information you need in one device.  Verify 
correct wiring to avoid damage.

Use the PSMR1 to check supply line phase 
orientation for devices such as scroll 
compressors or motors. Works on 45-70 Hz 
and on voltages between 100 and 600 VAC. 
Five indicators give you information about 
open phases, and indicate the sequence of the 
three lines. Use the motor rotation tester side 
of the meter to verify the rotation direction of 
the motor shaft.

Note:

 

Follow all warnings to ensure 

safe operations.

Safety Notes

    •  Read the following safety information 

carefully before attempting to operate or 
service the meter.

    •  Use the meter only as specified in this

manual; otherwise the protection provided 
by the meter may be impaired.

    •  Rated environmental conditions:

        1.  Indoor use.
        2.  Installation Category III.
        3.  Pollution Degree 2.

        4.  Altitude up to 6560 feet (2000 meters).
        5.  Relative humidity 80% Max.
        6.  Ambient temperature 32 - 104˚F (0 - 40˚C).

    •  Observe the international electrical symbols 

listed below:

 Meter is protected throughout by double  
 insulation or reinforced insulation.

 WARNING! 

Risk of electric shock.

 CAUTION! 

Refer to this manual before 

 using the meter.

 Alternating current.

Features

    •  Three functions in one unit including open phase, 

      phase sequence and motor rotation indication.

    •  This model is ideal for installing conveyor lines,   

      pump systems and interconnected drivers.

    •  Identifies 3-phase sequence and open phase check.

    •  Battery operated.

    •  Meets EN61010-1 safety requirements.

    •  Complete with three large alligator clips.

Descriptions

    1.  Phase rotation input terminal

    2.  Open phase indicator

    3.  Phase rotation indicator

    4.  Motor tester power switch

    5.  Motor tester power indicator

    6.  Motor rotation indicator

    7.  Motor rotation input terminal

Measuring Methods

Operations 3 phase rotation tester:

        1.  Connect the test lead to 3-phase input 

terminals by R-S-T.

        2.  Connect color alligator clips to the 

terminals of a 3-phase power source. 
Connecting order may be optional.

        3.  Make sure that all of the three lamps for 

open phase check are on. If so, there is no 
open phase. When any of the three lamps 
is not on, there is open phase.