![UEi 053533508215 Instruction Manual Download Page 2](http://html1.mh-extra.com/html/uei/053533508215/053533508215_instruction-manual_834482002.webp)
2.
Pressure Probe (WPP1): Hub 4 & Hub 6
A.
Cable connector plug-in: for connecting the
pipe clamp sensor (WPC1).
B.
Battery cover
C.
Light: Blinks
GREEN
when probe is powered
on and blinks
RED
when low battery.*
D.
Power Button: Hold for one second to
power on
E.
1/4”pressure connector
F.
1/4” pass-through connector
*NOTE:
Low battery indicator is in the “Tool
Connection” screen
GENERAL SPECIFICATIONS
Operating Temperature:
14°F to 158°F
(-10°C to 70°C)
Storage Temperature:
14°F to 140°F
(-10°C to 60°C)
Operating Humidity:
30% RH to 85% RH
Over-range:
1000 PSI
Dimensions:
6.70 in x 1.56 in x 1.44 in
(17 cm x 4 cm x 3.7 cm)
Item Weight:
7.4 oz (210 gr)
Certification:
CE Conformity, FCC/IC
Battery Type:
(AA) 2
Battery Life:
100+ hours
3. Pipe clamp sensor (WPC1): Hub 4 & Hub 6
A.
Temperature sensor
B.
Cable connector plug-in: for connecting
WPC1 to the WPP1.
NOTE:
Maximum pipe diameter for WPC1 is 1.5 in.
GENERAL SPECIFICATIONS
Operating Temperature:
-40°F to 185°F
(-40°C to 85°C)
Storage Temperature:
14°F to 140°F (-10°C to 60°C)
Dimensions:
5.66 in x 3.81 in x 1.10 in
(14.4 cm x 9.7 cm x 2.8 cm)
Item Weight:
2.1 oz (60 gr)
Certification:
CE Conformity, FCC/IC
A.
Home Screen:
Refrigerant Side
A.
Home Screen:
Air Side
UEi HUB OVERVIEW
B.
A.
A.
B.
C.
D.
E.
F.
WPP1 OVERVIEW
WPC1 OVERVIEW
A. Suction Line Pressure
B. Suction Line Temperature
C. Refrigerant Favorites (tap to view)
D. Liquid Line Pressure
E. Liquid Line Temperature
F. Refrigerant List (tap to view)
G. Air Side Screen (tap or swipe
left to view)
H. Vapor Saturation Temperature
I. Liquid Saturation Temperature
A. Refrigerant Side Screen (tap or
swipe right to view)
B. Delta T
C. Target Delta T (assumes
400 CFM/ton)
D. Return Dry Bulb Temperature
E. Return Wet Bulb Temperature
F. Return and Supply Calculations
(tap to view)
G. Supply Dry Bulb Temperature
H. Supply Wet Bulb Temperature
Hub
Refrigerant Side
Air Side
Line Pressure
Line Temp
select tool
select tool
Suction
--.--°F
Vapor
Saturation
--.--°F
Superheat
Line Pressure
Line Temp
select tool
select tool
Liquid
--.--°F
Liquid
Saturation
--.--°F
Subcooling
R507A
A.
F.
G.
I.
H.
B.
C.
D.
E.
Hub
Refrigerant Side
Air Side
--.--°F
Delta T
--.--°F
Target Delta T
Supply Dry Bulb
Supply Wet Bulb
select tool
select tool
Return Dry Bulb
Return Wet Bulb
select tool
select tool
G.
F.
B.
A.
C.
D.
E.
H.
• Remove battery cover.
• Replace the old batteries with 2 new
(AA) batteries.
• Replace the battery cover.
Battery level
are displayed in the tool
connection screen to the right of each
probe connected.
Caution
: Take care not to lose the screws when
opening battery compartments
www.
GlobalTestSupply
.com
Find Quality Products Online at: