background image

4

With Switch Rating Code A

Function

Wire Gauge/Color

Switched Output (5 to 30 VDC, 100 mA max.)

*

20

AWG/Brown

IAW Output (5 to 30 VDC, 100 mA max.)

*

20 AWG/Orange

4 - 20  mA Output - Positive (+) (Optional) 20 AWG/Yellow

Power Supply Input + (18 - 30 VDC)

20 AWG/Red

Power Supply and Signal Ground

20 AWG/Black

With Switch Rating Code B

Function

Terminal Label

No Connection

Blank

Switched Output (5 - 30 VDC, 100 mA max.)

*

SWT-OUT

IAW Output (5 - 30 VDC, 100 mA max.)

*

IAW

4 - 20 mA Output - Positive (+)  (Optional) 4-20MA

Power Supply Input + (18 - 30 VDC)

+ VDC

Power Supply and Signal Ground

COMMON

With Switch Rating Code C

Function

Terminal Label

Switch Supply - IN(280 VAC, 15 A max.)

VAC-HI

Switched Output - OUT(280 VAC, 15 A max.)

LOAD

IAW Output (5 - 30 VDC, 100 mA max.)

*

IAW

4 - 20 mA Output - Positive (+)  (Optional) 4-20MA

Power Supply Input + (18 - 30 VDC)

+ VDC

Power Supply and Signal Ground

COMMON

* Supply voltage on low voltage switched output (rating code A
& B) and the IAW output, must never exceed the unit's power
supply input voltage.

THEORY OF OPERATION

The One Series electronic switch evaluates the measured
process variable and switches the output ON or OFF based on
the set point & deadband values, and the selected switch mode.
Programmable features such as set point, deadband and switch
mode determine how the product is to operate and at what
values.

 

The 

SET POINT

 is the value at which the output switch turns

ON or OFF to initiate an alarm or shutdown sequence.
See Setting of User Parameters - Set Point.

 

The 

DEADBAND

 setting determines the difference above

or below set point at which the output switch will reset after
the set point has been reached.  See Setting of User
Parameters - Deadband.

 

The 

SWITCH MODE

 setting determines if:

 

The switched output is ON or OFF above or below
the set point value (NO or NC).

 

The local status indicator flashes to indicate the
switch output has tripped either above or below
the set point value.

 

The I Am Working (IAW™) signal flashes either
above or below the set point value.

 

The deadband is above or below the set point
value.

 

See Setting of User Parameters - Switch Mode.

 

The 

- Extreme

 and 

+ Extreme

 are the minimum and

maximum process values (lowest and highest) sensed by the
product.  This provides a snapshot of process variations since
the last time these values had been reset by the user.

A local status indicator (LED) aids the user in determining the
switch output state.  When the LED is illuminated continuously, it
signifies normal operation (no fault condition).  A flashing LED
signifies a tripped condition (an alarm or shutdown condition,
process variable has surpassed the set point value).  If the LED
is not illuminated, it signifies the switch has lost power or is not
able to function properly.  Whether the LED output is ON above
or below the set point is determined by the

 

SWITCH MODE

setting.

I Am Working (IAW™) signal provides a remote signal which
can be used to determine the “health” of the product.  It can also
be used to determine whether the output has tripped.  The
IAW™ signal has three (3) states:

 

ON when the product is powered, and internal diagnostics
determine that it is functioning properly and the output has
not tripped.

 

OFF when product has lost power or the internal
diagnostics have indicated a failure.

 

Flashing ON and OFF (in 50 ms. intervals) to indicate that
the product is functioning properly but the output has
tripped

.

The IAW™ output is an open drain (collector) output which may
be used as a signal to a PC, PLC or DCS logic input or to drive
a 5 to 30 VDC (100 mA max.) indicator lamp. The internal
diagnostics test the “health” of the microprocessor, sensor,
firmware and power supply for
proper operation.

NOTE:

  The power supply voltage for the IAW™ output must

not exceed the power supply input to the device.

The Switched Output may be used in a number ways to provide
local control of the alarm/shutdown circuit, eliminating the need
for remote monitoring, interpretation, and switching logic
algorithms in a PLC, DCS or computer.  The One Series’
switched output is intended to initiate an alarm or shutdown
sequence locally and independent of other interpretive devices.
Either the low level open drain output or the optional high current
solid-state relay provide fast, reliable switching in the field at the
point of measurement.  The switched output is designed as a
fail-safe-open circuit so that if the One Series loses power the
output will open.

The standard, open drain output may be used to trigger logic
level circuits to initiate an alarm or shutdown sequence.  The
optional high level solid-state relay is intended to switch loads
directly such as relays, contactors or moderate AC voltage
loads.

NOTE:

  The power supply voltage for the low level version of

the switch output must not exceed the power supply input to the
device.

A LCD digital display (user adjustable version only)

 

provides

additional information such as process variable (both numeric
and in a bar graph format), units of measure, and switch status.

Summary of Contents for ONE Series

Page 1: ...OR ELECTRICAL WIRE ENTRY DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS THIS IS ESPECIALLY CRITICAL FOR LOCAL MOUNT TEMPERATURE UNITS The One Series product may be mounted in any position providing the electrical conduit connection is not facing up See Diagrams 1 and 2 Ensure the process connection is sealed to the process port to prevent leakage Process Connections PRESSURE ...

Page 2: ... AND VOLTAGE LEVELS BE CONFIRMED PRIOR TO POWERING THE UNIT IF ERRANT SWITCHING OF THE OUTPUT WILL HAVE ADVERSE AFFECTS ON THE SYSTEM ENSURE THAT THE OUTPUT S ARE NOT CONNECTED UNTIL THE PRODUCT HAS BEEN CONFIGURED APPROPRIATELY IAW Output Connections The One Series 100 mA open drain IAW output is a sinking output which completes the circuit to the circuit common The power for the IAW output must ...

Page 3: ... the switched signal connected to the device under control LOAD Wire the output as follows per Diagram 11 The power source connects to the terminal marked VAC HI The load connects to the terminal marked LOAD The other load connection is to the power source return Optional 4 20 mA Analog Process Signal Output The One Series 4 20 mA output signal is intended for remote monitoring or trending of the ...

Page 4: ...he LED is illuminated continuously it signifies normal operation no fault condition A flashing LED signifies a tripped condition an alarm or shutdown condition process variable has surpassed the set point value If the LED is not illuminated it signifies the switch has lost power or is not able to function properly Whether the LED output is ON above or below the set point is determined by the SWITC...

Page 5: ...rns to the normal operating mode and new data is NOT saved An optional 4 to 20 mA analog current output is available to provide a remote indication of the process variable relative to the full scale range of the product The output signal is proportional over the operating range of the unit 4 mA at the minimum range value 20 mA at the maximum range value The output is non isolated capable of drivin...

Page 6: ...rm if SP 300 Deadband 50 switch energizes at 300 and de energizes 250 To display the SET POINT value press the ñ arrow key X XXX psi Set Point X XXX NOTE If there is no keypad activity for approximately 4 seconds the unit returns to normal operation TO CHANGE THE SET POINT VALUE 1 First display the SET POINT value by pressing the ñ arrow key 2 Simultaneously press the ï and ð keys A cursor will fl...

Page 7: ...NOTE Consider the SWITCH MODE and operating range when determining set point and deadband values to ensure that the reset value is within the operating range For example if the unit is operating in a High Limit Shutdown Mode the set point is 25 psi and the deadband is 30 psi the output will trip OFF but never reset Extreme Values The Extreme and Extreme are the minimum and maximum process values l...

Page 8: ...8 Diagram 1 Single Enclosure Version no terminal block or solid state relay Diagram 2 Dual Enclosure Version for terminal block and solid state relay options Diagram 3 ...

Page 9: ...ers Local Mount Low Temperature High Temperature Pressure Sensor Remote Remote Diagram 5 Local Mount Versions Model DIM L IN L1 4 L2 6 L3 10 Remote Mount Versions Model DIM L FT R1 6 R2 10 R3 20 High Temperature Version Model DIM L FT H1 6 H2 10 H3 20 Diagram 4 ...

Page 10: ...10 Diagram 6 Diagram 7 Diagram 8 ...

Page 11: ...11 Diagram 9 Diagram 10 Diagram 11 Diagram 12 ...

Page 12: ...12 Diagram 13 ...

Page 13: ...literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Use only factory authorized replacement parts and procedures Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY OF REPAIR AND REPLACEMENT UE warrants tha...

Reviews: