UE 2SLP Installation And Maintenance Instructions Manual Download Page 5

IM_ONE_Safety-07

www.ueonline.com

5

PART II - WIRING

 

Removing the One Series 

Field Safety System™

 Enclosure Cover and Display Module

TO PREVENT ELECTROSTATIC DISCHARGE WIPE DOWN COVER AND ENCLOSURE OF ANY DUST BUILD-UP BEFORE REMOVING COVER.

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING DEVICE. WIRE DEVICE IN ACCORDANCE WITH LOCAL AND 

NATIONAL ELECTRICAL CODES.  MAXIMUM RECOMMENDED WIRE SIZE AND RECOMMENDED TIGHTENING 

TORQUE FOR FIELD WIRING TERMINAL BLOCKS ARE SHOWN WITHIN TABLE 2 (PAGE 5).

TO PREVENT SEIZURE OF ENCLOSURE COVER, DO NOT REMOVE LUBRICANT.  THREADS SHOULD ALSO BE FREE OF DIRT 

AND OTHER CONTAMINANTS.

Remove the enclosure cover by turning it counter-clockwise for 8 revolutions (Figure 3). Carefully remove the display 

module by grasping the outer edge and pulling it away from the base enclosure (Figure 4), being careful not to 

strain any of the wired connections.  Allow the display module to hang from the wired connections to access the base 

enclosure and terminal blocks for wiring.  Do not remove the display module wire assemblies.  Insert the field wiring 

through the conduit opening(s) of the base enclosure.  Make the connections as shown within the wiring diagrams 

(Figure 5-6, page 6).  

The primary chassis and equipment grounding terminal

 is provided inside the 

base enclosure.
Cleaning the display and keypad surface should be performed with a damp cloth only.  Do not attempt to wash down 

the One Series with the cover removed.

 Tools Required: 

Small flat-head screwdriver; wire strippers

TO PREVENT IGNITION, DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER.  KEEP COVER TIGHT WHILE IN OPERATION.  DO NOT 

DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

DO NOT REPLACE COMPONENTS UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS. 

THE DEVICES SHALL BE PROPERLY GROUNDED IN THE END USE APPLICATION USING THE GROUND SCREWS PROVIDED WITH THE 
ENCLOSURE.

FIELD WIRING MUST BE RATED 105°C MINIMUM.  FOR AMBIENT TEMPERATURES BELOW -10

°

C, USE SUITABLE FIELD WIRING.  

MODEL 2SLP IS LOOP-POWERED AND OBTAINS OPERATING POWER FROM THE 4-20 mA LOOP.  THE POWER SUPPLY PROVIDING POWER TO THE LOOP 

MUST BE CLASS 2 OR SELV AND CURRENT LIMITED.  THE MAXIMUM LOAD RATING FOR THE SAFETY RELAY OUTPUT (SRO) IS SHOWN IN TABLE 3 ON PAGE 

6.  OVERLOADING THE SAFETY RELAY OUTPUT (SRO) MAY CAUSE FAILURE.  THE SRO MUST NOT BE CONNECTED DIRECTLY TO A POWER SUPPLY WITHOUT 

A SUITABLE SERIES LOAD.

 

Terminal Block and Torque Details

Description

Max. Wire Gauge

Min. Wire Gauge

Recommended Tightening Torque

TB1

3-Position

14 AWG

22 AWG

3.50 in-lbs. or 0.4 Nm

TB2

4-Position

14 AWG

26 AWG

3.50 in-lbs. or .4 Nm

TB3

2-Position

16 AWG

26 AWG

2.2 in-lbs. or .25 Nm

TB4

2-Position

16 AWG

26 AWG

2.2 in-lbs. or .25 Nm

NOTE: 

The sensor’s 4-conductor ribbon cable assembly must remain connected to the display module with the red wire oriented to the arrow on 

the label at the rear of the module.  Reversing this connector will result in measurement errors or failure.  Please refer to the wiring diagrams 

beginning on page 6.

Figure 3

Figure 4

Table 2

Summary of Contents for 2SLP

Page 1: ... HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Cert Number UL File E226592 DEMKO 09 ATEX 0813748X IECEx UL 08 0017X Applicable Standards UL 50 UL 50E UL 61010 1 UL 1203 CSA C22 2 No 25 1966 CSA C22 2 No 30 M1986 CSA C22 2 No 94 01 07 CSA C22 2 No 9...

Page 2: ...Series transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connected directly to the final element and replacing a transmitter safety relay trip amplifier and logic solver It has an embedded high capacity programmable safety relay that provides extremely fast respo...

Page 3: ...By pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values recorded in memory MAX XX XX MIN XX XX The display will automatically revert back to the Process Display mode after scrolling ALARM CONDITION When the process goes beyond the set point the display will beg...

Page 4: ...ure that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corrosion resistant material 5 threads engaged minimum with thread sealant is required to maintain enclosure type 4X IP66 For Remote Sensing Route the extension wire to avoid contact with live components ...

Page 5: ...oved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS DO NOT REPLACE COMPONENTS UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS THE DEVICES SHALL BE PROPE...

Page 6: ... diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus terminals In this wiring configuration power is provided for all switching and diagnostic functions but a 4 20 mA output is not possible This alternative method of powering the One Series Field Safe...

Page 7: ...ut function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver The final element is controlled by the logic solver Total wire connections 4 The 4 20mA signal is used by the logic solver to initiate the safety function IAW provides a separate indication of devic...

Page 8: ...s Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommends monitoring the IAW signal to maximize the safe failure fraction in an SIS application Additionally wiring the SRO to an external load final element is not required For direct control of a final ele...

Page 9: ...000 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperature sensor is subject to 103 25 to 110 of range or when the pressure sensor is subject to 103 25 to 150 of range Fault 0 FAULT CURRENT In addition to the discrete IAW and Safety Relay Output status si...

Page 10: ...ft 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR MAX MIN or MAN RSET if Latch is set will appear on the display This is the first command prompt in the Programming Mode NOTE The Field Safety System will automatically exit the Programming Mode and ...

Page 11: ... opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low Please use the Safety Relay Output Decision Logic Figure 13 page 12 for help with setting the appropriate Safety Relay Output mode Press and release the left 2 button until the desired mode appears Pr...

Page 12: ...16 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile memory The max min values may be viewed at any time by removing the enclosure cover page 5 and pushing the left 2 button The display will scroll the MAX MIN values and then return to the Process Disp...

Page 13: ... and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to enter the new offset and return to the main menu Adjusting Span SPAN provides an adjustment to shift the slope of the sensor s response curve to accommodate an offset value other than zero To adjust SPAN...

Page 14: ...lity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does not change by the amount and selected time period the display will indicate PLUG and the IAW Output will open indicat ing a fault Refer to the Programming Flowchart on page 19 Enter the Programming Mod...

Page 15: ...cations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software digital filter with a configuration time constant for sup pressing certain transient short duration events Refer to the Programming Flowchart on page 19 Enter the Programming Mode see page 10 and mov...

Page 16: ... left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digit This process value must be between 3 and 25 of the sensor s maximum range Press the right g button to enter the new scale and return to the main menu Setting the 20 mA portion of the scale see Figu...

Page 17: ...pen check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagnostic Fault Relay Monitor The relay output fault monitor circuit has detected that the output state of the solid state relay is incorrect This feature must be enabled in the menu Check the wiring conn...

Page 18: ...E ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES REV ECN Figure 19 Kanban number and Date Code Set Point Reached IAW Fault SRO Status IAW Output Safety Relay Output No No Closed Closed Closed No Yes Open Open Open Yes No Open Closed ...

Page 19: ...pend on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blinking Digit Sets Digit and moves to next SPAN POS NEG 8888 Set Blinking Digit Increments Blinking Digit Sets Digit and moves to next Offset out of Range flash Err SPAN out of Range flash Err PLUG PORT...

Page 20: ...OR PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 264 16 mm 203 2 mm 137 16 mm 129 54 mm 134 62 mm 137 16 mm 76 2 mm 92 20 mm 129 54 mm 134 62 mm 137 16 mm 107 95 mm 61 91 mm 158 75 mm 7 11 mm 107 95 mm 76 2 mm 6 35 mm 8 73 mm DIMENSIONAL DRAWINGS GAG...

Page 21: ...SULATED CABLE Ø0 125 3 18 mm FOR DC UNITS Ø0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT PIPE NIPPLE 300 SERIES st st 0 50 12 7 mm Temperature Sensors Remote TR1 TRC TH1 THC TC1 TCC SENSOR OPTIONS Spring Loaded Local TTC Fixed Local TL1 TL3 Differential Pressure 1 4 18 NPT MALE BOTH ...

Page 22: ...ée de fil électrique Ne pas monter l unité à des températures ambiantes dépassant les limites publiées Cela est particulièrement important pour les unités de tem pérature à montage locale L utilisation envelopper est recommandée lorsque le soleil et la pluie peuvent entrer en contact avec le boîtier 1 In order to meet the electromagnetic compatibility requirements specified in EN61000 6 2 Im munit...

Page 23: ... retirer le couvercle du boîtier Maintenir le couvercle fermé pendant le fonctionnement Ne pas décon necter l équipement que lorsque l alimentation est coupée ou que la zone est connue pour être non explosives 5 Do not replace components unless power has been switched off or the area is known to be non hazard ous Ne remplacez pas les composants avant que le courant soit coupé ou que la zone est co...

Page 24: ...or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national electrical codes using wire size recommended in installa tion sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon ...

Reviews: