PARAMETER DESCRIPTION
*
x
refers to channel number, can be 1~2, 1~4, 1~6 for AI-702M, 704M and 706M respectively.
Parameter
Name
Remarks
Setting range
H.ALx
High limit alarm
x channel high alarm on when PVx (the present value of x
channel)>H.ALx;
Alarm releases when PVx<H.AL - dFx.
Set H.ALx maximum value will disable function
-1999~+9999
★
or
defined unit
L.ALx
Low limit alarm
x channel low alarm on when PVx<L.ALx;
Alarm releases when PVx>L.ALx + dfx.
Set L.ALx minimum value will disable function
dFx
Dead band
dF is set to avoid high frequent alarm on/off actions
caused by process input fluctuation.
0~999.9
★
or
0~9999 units
Snx
Input
specification
Sn
Input spec.
Sn
Input spec.
0
K
1
S
2
R
3
T
4
E
5
J
6
B
7
N
8
WRe3-WRe25
9
WRe5-WRe26
10
Extended
input spec.
11~18
Spare
19
BA2 (JPt100)
20
Cu50
21
Pt100
22
Pt100
(-100.00~+300.00)
★
23~24
Spare
25
0~75mV
26
0~80ohm
27
0~400ohm
28
0~20mV
29
0~100mV, 0~5V (J3);
0~20mA (J4)
30
0~60mV
31
0~1V
32
0.2~1V ;
two-wire
re-transmitter
(J5)
33
1~5V voltage (J3)
4~20mA current (J4)
38
Extraction for
range: 0.2~1V
39
Extraction for range:
1~5V (J3)
4~20mA (J4)
Note: Input spec. should be compatible with input module.
For those spec. unknown, use J1 for thermocouple and
mV inputs, J2 for two-wire RTD, and J0 for three-wire
RTD.
Multiplication: set
Sn3=40, PV3=PV1 x PV2 (PV refer to
input value)
Summation: set Sn3, Sn4, or Sn5 =41, its input is the sum
of the inputs of previous channels, e.g. when Sn5=41,
PV5=PV1+PV2+PV3+PV4.
Subtraction: set Sn3=42, PV3=PV2-PV1
0 ~ 39