103
105294-05 - 5/15
Appendix B - (continued)
Model
No.
Fuel
Measured CO
2
Approximate De-rate per 1000 Ft.
2000-4500 ft.
4501-7800 ft. 7801-10,200 ft.
Derate/1000 ft.
2000-4500 ft.
Derate/1000 ft.
4501-7800 ft.
Derate/1000 ft.
7801-10,200 ft.
K2-080
NG
8.7-9.2
8.7-9.1
8.7-9.1
0%
0%
0%
LP
K2-100
NG
8.5-9.3
8.5-9.3
8.5-9.3
0%
0%
0.7%
LP
10.0-10.3
9.9-10.2
9.8-10.1
0%
0.9%
1.0%
K2-120
NG
8.8-9.3
8.8-9.3
8.8-9.3
0%
0%
0.6%
LP
9.9-10.2
9.9-10.2
9.5-9.8
0%
0.5%
0.6%
K2-150
NG
8.6-9.3
8.6-9.3
8.6-9.3
0%
0.4%
1.0%
LP
9.8-10.3
9.8-10.3
9.8-10.1
0.3%
1.2%
1.4%
K2-180
NG
8.5-9.1
8.5-9.1
8.5-9.1
2.0%
1.9%
1.7%
LP
9.9-10.3
9.9-10.2
No application
2.5%
2.4%
No application
NOTE: THESE DE-RATES ARE AT MINIMUM VENT LENGTH Max. Vent Length 135
eq. feet (3 inch Intake/Vent Pipe)
Table B1: K2 Altitude Adjustments (Above 2000 ft. only)
Model No.
# Counter-Clockwise Turns
(From Fully Closed)
K2-080
3-3/4
K2-100
3
K2-120
4
K2-150
2-3/4
K2-180
6-1/2
Table B2: K2 LP Conversion Only
Summary of Contents for K2
Page 37: ...37 105294 05 5 15 THIS PAGE LEFT BLANK INTENTIONALLY ...
Page 84: ...84 105294 05 5 15 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Page 86: ...86 105294 05 5 15 X Wiring continued ...
Page 87: ...87 105294 05 5 15 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Page 97: ...97 105294 05 5 15 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Page 106: ...106 105294 05 5 15 ...
Page 107: ...107 105294 05 5 15 ...