Figure 8: Outdoor Reset Curve
Central Heat
Setpoint
Heating Element Type
Central Heat
Setpoint
Heating Element Type
180°F to 190°F
(82.2°C to 87.8°C)
Fan Coil
100°F to 140°F
(37.8°C to 60°C)
In Slab Radiant High
Mass Radiant
160°F to 190°F
(71.1°C to 87.8°C)
Convection
Baseboard
Fin Tube
Convective
130°F to 160°F
(54.4°C to 71.1°C)
Staple-up Radiant
Low Mass Radiant
130°F to 160°F
(54.4°C to 71.1°C)
Radiant
Baseboard
140°F to 160°F
(60°C to 71.1°C)
Radiators
i. Operation
F. Changing Adjustable Parameters (continued)