background image

USER GUIDE

u-line.com

General Installation

General Installation

LEVELING INFORMATION

1.  Use a level to 

confirm the unit is 
level. Level should 
be placed along top 
edge and side edge 
as shown.

2.  If the unit is not level, adjust the legs on the corners of 

the unit as necessary.

   

3.  Confirm the unit is level after each adjustment and 

repeat the previous steps as needed.

INSTALLATION TIP

If the room floor is higher than the floor in the cutout 
opening, adjust the rear legs to achieve a total unit rear 
height of 

1⁄8

” (3 mm) less than opening’s rear height. 

Shorten the unit height in the front by adjusting the front 
legs. This allows the unit to be gently tipped into the 
opening. Readjust the front legs to level the unit after it is 
correctly positioned in the opening.

INSTALLATION

1.  Plug in the power/electrical cord.

2.  Gently push the unit into position. Be careful not 

to entangle the cord or water and drain lines, if 
applicable.

3.  Re-check the leveling, from front to back and side to 

side. Make any necessary adjustments. The unit’s top 
surface should be approximately 

1⁄8

” (3 mm) below 

the countertop.

4.  Install the anti-tip bracket.

5.  Remove interior packing material and wipe out the 

inside of the unit with a clean, water-dampened cloth.

1

Turn to Adjust

11

Summary of Contents for ORE124

Page 1: ...USER GUIDE SERVICE MANUAL Model UORE124 SS01A ...

Page 2: ... Door Swing Door Adjust Interior Adjustments Maintenance Free Standing Kit Cleaning Cleaning Condenser Extended Non Use Operating Instructions First Use Control Operation Airflow and Product Loading Service Troubleshooting Wire Diagram Product Liability Warranty Claims Parts Ordering Replacement Parts R600a Specifications System Diagnosis Guide Compressor Specifications Troubleshooting Extended Co...

Page 3: ...ine RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE PRODUCT INFORMATION Looking for additional information on your product User Guides Spec Sheets CAD Drawings and Product Warranty information are available digitally on u line com PROPERTY DAMAGE INJURY CONCERNS In the unlikely event property damage or personal injury is suspected related to a U Line product please take the following steps 1 U Line Cu...

Page 4: ...r or moderate personal injury property or equipment damage This unit contains R600a Isobutane which is a flammable hydrocarbon It is safe for regular use Do not use sharp objects to expedite defrosting Do not service without consulting the R600a specifications section included in the User Guide Do not damage the refrigerant circuit Service must be done by factory authorized service personnel Any p...

Page 5: ...in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations regarding the disposal and recycling of refrigeration appliances and follow these steps completely 1 Remove all consumable contents from the unit 2 Unplug the electrical cord from its socket 3 Remove the door s drawer s DANGER 5 ...

Page 6: ... or reduce ice production on applicable models For best performance keep the unit out of direct sunlight and away from heat generating equipment In climates where high humidity and dew points are present condensation may appear on outside surfaces This is considered normal The condensation will evaporate when the humidity drops CAUTION Damages caused by ambient temperatures of 40 F 4 C or below ar...

Page 7: ...the unit Always keep your working area dry NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that has been placed by a qualified electrician The unit requires a grounded and polarized 115 VAC 60 Hz 15A power supply normal household current An individual properly grounded branch circuit or circuit break...

Page 8: ...N Unit can NOT be installed behind a closed cabinet door CUTOUT DIMENSIONS 24 cutout width sufficient if door protrudes beyond adjacent cabinetry PRODUCT DIMENSIONS REAR FRONT TOP SIDE 13 1 8 333 mm 18 3 8 467 mm 22 1 8 562 mm 26 680 mm 22 572 mm 24 3 8 619 mm 1 25 mm 4 102 mm 7 178 mm 24 610 mm 24 1 4 616 mm 34 1 8 867 mm to 35 1 8 892 mm Preferred location for electrical outlet is in adjacent ca...

Page 9: ...ced according to each unit s electrical specifications requirements Side by Side Installation with Bracket 1 Slide both units out so screws on top of units are easily accessible 2 Remove screws as shown below 3 Place bracket over holes and attach to unit with two screws removed in step 2 using a T 25 Torx driver Tighten screws fully 4 Gently push units into position Be careful not to entangle the ...

Page 10: ...over holes and attach to unit with two screws removed in step 2 using a T 25 Torx driver Tighten screws fully 4 Gently push unit into position Be careful not to entangle the electrical cord or water line if applicable 5 Check to be sure the unit is level from front to back and side to side Make any necessary adjustments The unit s top surface should be approximately 1 8 3 mm below the countertop 6...

Page 11: ...an opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Readjust the front legs to level the unit after it is correctly positioned in the opening INSTALLATION 1 Plug in the power electrical cord 2 Gently push the unit into position Be careful not to entangle the cord or water and drain lines if applicable 3...

Page 12: ... are SHARP and can be easily damaged Removing the grille 1 Disconnect power to the unit 2 Loosen the two screws 1 3 Remove grille 2 from unit Installing the grille 1 Align cabinet and grille holes and secure but do not over tighten grille screws 1 Note When installing next to a 15 wide U Line product use the supplied spacers behind the grille The 24 grille will now be on the same plane as the 15 g...

Page 13: ...ing Units have a zero clearance for the door to open 90 when installed adjacent to cabinets Stainless Steel models require 2 1 8 54 mm door clearance to accommodate the handle if installed next to a wall Wall 90 Door Swing 2 1 8 Min 54 mm 13 ...

Page 14: ... Loosen do not remove top and bottom hinge screws using a Torx T 25 screwdriver 3 Align door squarely with cabinet 4 Make sure gasket is firmly in contact with cabinet all the way around the door no gaps 5 Tighten bottom hinge screws 6 Tighten top hinge screws and replace hinge cover REVERSING THE DOOR Location of the unit may make it desirable to mount the door on the opposite side of the cabinet...

Page 15: ...rews on either side Install bottom hinge Install two or three screws depending on model Replace nuts if used Install top hinge and door 1 Remove pivot screw from hinge flip hinge over and install the pivot screw in the same hole from the opposite surface 2 Lift the door onto the bottom hinge 3 Align edge of the hinge with the outer edge of the unit while inserting pivot screw into top of door 4 Ti...

Page 16: ...al screw in back of base 3 Align front hole wit hole in shell accessory hole in base and hole in grille Tighten screw USER GUIDE Free Standing Kit u line com Free Standing Kit The free standing kit is an optional accessory used when unit is freestanding not built into a cabinet To install the kit 1 Remove grille see GRILLE INSTALLATION section 2 Place shell accessory over front and back of cabinet...

Page 17: ...n for more details NOTICE Temperature displayed reflects actual temperature inside unit If the temperature displayed is different than selected the unit is progressing towards the selected temperature Time to reach set point varies based upon ambient temperature temperature of product loaded door openings etc U Line recommends allowing the unit to reach set point before loading 17 ...

Page 18: ...for 5 seconds The display will change units Enable Sabbath Mode Press and hold for 5 seconds and release The oF oC symbol will flash briefly after 5 seconds Interior light and display will go dark and remain so until user resets mode unit continues to operate Disable Sabbath Mode Press and release Display and interior light return to normal operation Showroom Mode Hold and for 5 seconds Display wi...

Page 19: ...nd sizes Not all bottles and cans will fit on every shelf and wine rack Larger diameter champagne and Magnum bottles only fit on wine racks when noted on the product specifications When determining capacities U Line uses typical 12 oz cans 12 oz bottles 750 mL white wine and red wine bottles shown below Airflow and Product Loading Typical Can 12 oz 4 123 mm 66 mm 2 27 32 19 32 Typical Bottle 12 oz...

Page 20: ...he shelves as follows 1 To move to a different position in the unit insert shelf at an angle approximately 15 20 over the rib in the side of the unit where you want to place the shelf Place the shelf into the unit at an angle to clear the door 2 Continue to slide the shelf into the unit at an angle until it clears the door Lower the shelf and push it in completely Ensure the raised edge strip is t...

Page 21: ...less steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be possible Integrated Models To clean integrated panels use household cleaner per the cabinet manufacturer s recommendation INTERIOR CLEANING Disconnect power to the unit Clean the interior and all removed components using a mild nonabrasive detergent...

Page 22: ...r sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in an open position 2 in 50 mm minimum 4 Allow the frost to melt naturally 5 After the frost melts completely clean the interior and all removed components See INTERIOR CLEANING 6 When the interior is dry reconnect power and turn unit on 22 ...

Page 23: ...environmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric power to the unit before cleaning the condenser NOTICE DO NOT use any type of cleaner on the condenser unit Condenser may be cleaned using a vacuum soft brush or compressed air 1 Remove the grille See GRILLE INSTALLATION 2 Clean the condenser coil using a soft brush or vacuum cleaner 3 Install the ...

Page 24: ...on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to prevent formation of mold and mildew Open door a minimum of 2 50 mm to provide the necessary ventilation WINTERIZATION If the unit will be exposed to temperatures of 40 F 5 C or less the steps above must be followed For questions rega...

Page 25: ...compressor makes a hum or pulsing sound that may be heard when it operates BEFORE CALLING FOR SERVICE TROUBLESHOOTING GUIDE ELECTROCUTION HAZARD Never attempt to repair or perform maintenance on the unit before disconnecting the main electrical power Troubleshooting What to check when problems occur NORMAL OPERATING SOUNDS IF SERVICE IS REQUIRED Troubleshooting Evaporator Refrigerant flowing throu...

Page 26: ...ing the testing period 6 After 24 hours check the temperature of the water If required adjust the temperature control in a small increment see CONTROL OPERATION Causes which affect the internal temperatures of the cabinet include Temperature setting Ambient temperature where installed Installation in direct sunlight or near a heat source The number of door openings and the time the door is open Th...

Page 27: ...ue White Black N C 1 6 Evap Cond fan Light Evap temp Zone temp Door switch Compressor FUSE Programming U s e r I n t e r f a c e 42376_C If Applicable POWER CORD ASSEMBLY 220 240 VOLT PLUG LIVE BLACK 115V BROWN 220 240V NEUTRAL WHITE 115V DARK BLUE 220 240V 1 1 5 5 27 ...

Page 28: ...ized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial number of the unit it was removed from the date and the servicer who removed the part If the service technician determines the damage is the result of installation issues water connection drain etc the consumer would be notified and the is...

Page 29: ...ting for warranty labor Units must be registered prior to warranty submittal Customers may register at www U Line com A proof of purchase is required We also accept the following information to update warranty New construction occupancy documents Closing paperwork Final billing Remodel Warranty parts will be shipped at no charge after U Line confirms warranty status Please provide the model serial...

Page 30: ...AN 80 54217 00 10 DRIER 80 54055 00 11 EVAPORATOR ASSEMBLY 80 55411 00 12 EVAPORATOR COVER 80 55513 00 13 EVAPORATOR FAN 80 54321 00 14 EVAPORATOR FAN COVER 80 54320 00 15 GASKET DOOR 80 55498 00 16 GLASS SHELF BOTTOM 80 54274 00 17 GLASS SHELF TOP 80 54277 01 18 GRILLE 80 55597 00 19 HINGE ASSEMBLY 80 55418 00 20 HINGE COVER 80 55499 00 21 LED LIGHT STRIP AND COVER 80 54000 00 22 LEG LEVELERS 4 8...

Page 31: ...rms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the return of original parts we will inform you when the parts order is taken This requirement will be noted on your packing list A prepaid shipping label will be emailed to you Please enclose a copy of the parts packing list and be sur...

Page 32: ...ician must observe all federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fire extinguisher in the work area R 600a is heavier than air do not allow any leakage migration to low areas such as basements and stairs Never use a torch on a fully charged refrigeration syste...

Page 33: ...acuum pump and recovery equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing any part of the sealed system Only a clean dry leak free system should be charged with R 600a R 600A SPECIFICATIONS LABELING R 600a equipped products are labeled both the unit an...

Page 34: ...gerant is left within the system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the system must be purged with dry nitrogen and at least one access point open to the atmosphere When re brazing proper ventilation is required along with constant monitoring for the presence of R600...

Page 35: ... Install a Schrader Type access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the charging hoses Seal the Schrader Type access port a proper cap and seal must be used to close the system SUMMARY Safely handling R 600a requires proper procedures and training R...

Page 36: ...perature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near room temperature Very hot Top passes warm Lower passes cool near room temperature due to liquid Room temperature cool or colder Extremely cold near inlet Outlet below room temperature backing up Lower than normal Complete Restriction In de...

Page 37: ...earing an anti static wrist strap that is grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and S pins To measure the run winding resistance measure across the C and R pins Also check S to R and you should get the sum of the run and start windings To ensure the windings ...

Page 38: ...outputs located on the relay power board Included in this section are some diagnostic tips and of course if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 779 2547 for assistance NORMAL OPERATING SOUNDS All models incorporate rigid foam insulated cabinets to provide high thermal efficiency and maximum sound reduction for its internal working components D...

Page 39: ...Refer to 14 Error Log in Service Mode Thermistor failure Check Error Log in Service Mode OHM thermistor Frost Buildup Inside Unit Door Ajar or Restricted from Closing Check door clearance to adjoining cabinetry Check distribution of product in unit Evaporator fan not operating Use Relay Toggle Component Testing in Service Mode Thermistor failure Check Error Log Display Not Working Unit placed in S...

Page 40: ... into overload The compressor will automatically deactivate during an overload and will remain deactivated until the overload switch cools This could take some time It is important to allow the compressor at least 5 minutes off time between relay cycles 2 Toggle the relay Its related component should activate deactivate with the switching of the relay If it does not test component Other Suspected ...

Page 41: ...ed magnetic force pulls the reed to its contact and closes the circuit which turns the light and display off When the door is open the reed pulls away from the contact and opens the circuit If the door is left open for longer than 5 minutes the switch will trigger an error code and set an audible warning Magnet Close To Switch Door Closed Switch Closed Magnet Away From Switch Door Open Switch Open...

Page 42: ...u LED activated with button activation CONTROL FUNCTION GUIDE FUNCTION COMMAND NOTES Defrost Duration Enter menu by pressing for more than 5 seconds Use or to increase reduce defrost duration Press to select Display shows df defrosting This controls how long the unit defrosts Defrost Period Press once again Use or to increase reduce defrost period Press again Display shows the interval in which th...

Page 43: ...RE Zone Thermistor If the zone thermistor in the unit fails the unit will continue to cool in a backup mode Self Preservation Mode to preserve the integrity of the contents The unit will otherwise operate normally USER GUIDE u line com Thermistor Thermistors are used for various temperature readings Thermistors provide reliable temperature readings using a resistance which varies based on surround...

Page 44: ...oor units defrost every 12 hours of compressor runtime for 45 minutes If you have verified that the unit does not have an ambient air leak utilize the Control Operation Service section and adjust unit to defrost every 9 hours for 60 minutes 44 ...

Page 45: ...condensation that may have appeared on glass doors and shelves Note If the unit is set to sabbath mode the evaporator fan will no longer respond to the state of the door switch In order to operate efficiently the evaporator fan blade and vents should be unobstructed and free of any dust buildup Evaporator Fan Replacement Should the evaporator fan need to be replaced follow the steps below 1 Remove...

Page 46: ...rator cover vents and push air out at fan mounting location 15 Installation is the reverse of removal 16 Care must be taken to assure the bottom of the evaporator cover is reinstalled behind the front edge of the train trough 17 Use sealant gum to seal any openings at rear of unit before replacing rear cover 18 Reinstall unit taking care to level space and secure as found 46 ...

Page 47: ...od or other natural disasters The product must be installed operated and maintained in accordance with your product s User Guide The remedies described above for each warranty are the only ones that U Line will provide either under these warranties or under any warranty arising by operation of law U Line will not be responsible for any consequential or incidental damages arising from the breach of...

Reviews: