U-Line H-6513 Manual Download Page 7

PAGE 7 OF 9 

0217 IH-6513

MAINTENANCE CONTINUED

FUEL FILTER

The fuel filter should be cleaned at least twice per 

heating season. Clean the filter by rinsing it in clean 1-K 

Kerosene. Contaminated fuel could make cleaning the 

fuel filter necessary immediately.

NOTE: To remove, turn filter 90° counterclockwise. 

(See Figure 9)

SPARK PLUG

Clean and re-gap every 600 hours of operation, or 

replace as needed. After removing the spark plug, 

clean the terminals with a wire brush. Re-gap the 

terminals to 0.140". (See Figure 10)

PHOTOCELL

The photocell should be cleaned using a cotton swab 

dipped in alcohol or water at least once per heating 

season, or more depending on conditions. (See Figure 11)

PUMP PRESSURE

1.  While heater is operating, turn adjusting screw 

clockwise to increase, counterclockwise to 

decrease pressure. (See Figure 12)

2.  Correct pump pressure is as follows:

MODEL NUMBER

PUMP PRESSURE

H-6513

5.5 PSI

H-6514

8.5 PSI

NOZZLES

Nozzles should be cleaned or replaced at least once 

per heating season. Contaminated fuel could make this 

necessary immediately.

1.  To clean dirt from nozzle, blow compressed air 

through nozzle front. (See Figure 13)

NOTE: It may be necessary to soak the nozzle 
in 1-K kerosene to loosen any dirt particles. 

Figure 9

Fuel Filter

Fuel Line

Side 

Cover

Figure 10

Burner 

Head

Spark 

Plug

Gap

Ignitor 

Wire

Figure 11

Photocell

Photocell 

Wire

Photocell 

Lens

Figure 12

Pressure Valve

Adjusting Screw

Figure 13

Nozzle Face

Burner Head

Nozzle

Summary of Contents for H-6513

Page 1: ...WARNING Fire burn inhalation and explosion hazard Keep combustibles such as building materials paper or cardboard a safe distance away from the heater Never use the heater in spaces which contain prod...

Page 2: ...s For outdoor use Indoor use permitted only for the temporary heating of adequately ventilated buildings or structures under construction alteration or repair Provide at least a three square feet open...

Page 3: ...60Hz AMPS 2 3A 2 7A PHASE Single Single Fuel Tank Lamp Drain Plug Power Cord Side Cover Fuel Cap Fuel Gauge Lower Shell Hot Air Outlet Front Handle Upper Shell Rear Handle Fan Guard Side Cover Digita...

Page 4: ...crews are secure 7 Attach rear handle with two 50 mm screws and two nuts through the third hole from the rear of the heater on either side See Figure 2 NOTE You will secure the rear handle in step 10...

Page 5: ...soning Use heater only in well ventilated areas Refer to Safety Warnings on pages 1 and 2 for information about carbon monoxide poisoning DANGER Carbon monoxide poisoning may lead to death Always prov...

Page 6: ...E To order parts call Uline Customer Service at 1 800 295 5510 Follow a maintenance schedule as follows FUEL FUEL TANK Flush tank every 200 hours of operation as needed NOTE Follow the long term stora...

Page 7: ...ng season or more depending on conditions See Figure 11 PUMP PRESSURE 1 While heater is operating turn adjusting screw clockwise to increase counterclockwise to decrease pressure See Figure 12 2 Corre...

Page 8: ...k CN2 CN2 CDS R TH Black Power Switch Power Plug AC 120 V 60Hz Limit Control Ignitor Pump Motor Black Black Black Black Spark Plug White White White White Green Earth Earth Earth Yellow Capacitor 20uF...

Page 9: ...sure Clean or replace spark plug Adjust plug gap as necessary Clean or replace fuel filter Clean or replace nozzle Rinse fuel tank with clean fresh kerosene Inspect all electrical connections See wiri...

Reviews: