background image

PAGE 3 OF 4 

1216 IH-6224

OPERATION

TEST EYEWASH UNIT

1.  After completing installation, test the eyewash 

station for proper operation by pulling down the 

tray. Check for proper water flow and quickly close 

the tray. Visually inspect the eyewash unit weekly 

for cleanliness and proper solution level (per ANSI 

Standard Z358.1-2014). When the water level drops 

below the 15-minute fill line, the tank must be 

emptied and then refilled. (See Figure 3)

2.  Attach the eyewash inspection tag (included) to 

the eyewash unit. This tag is to be used for weekly 

inspection documentation. Hook-and-loop fasteners 

are provided to attach the tag to the unit.

3.  If the eyewash unit is not working properly, remove 

it from the hazard area and contact Uline 

immediately.

OPERATE EYEWASH UNIT

1.  Pull down the tray.

2.  Hold eyelids open with thumbs and forefingers. 

Rotate eyes back and forth to ensure a complete 

rinse.

3.  Allow water to bathe both eyes simultaneously for a 

minimum of 15 minutes.

4.  Seek medical attention immediately after use.

CAUTION! Do not lean on the eyewash tray 
when in the opened position. Damage to unit 

may result.