CCE25 / CCH25
Water connection
Pressure
1 bar (min.) to 6 bar (max.)
Quantity
At least 4 l/min
Temperature
max. 25°C
Diamond wire lengths
The diamond wire guard are obtained from:
• Constant = 331 cm
• 2x thickness of structure D
• Table value A depending on hole diameter
Hole diameter
Value A
50 cm
0
100 cm
55 cm
150 cm
115 cm
200 cm
140 cm
250 cm
170 cm
Formula:
L
total
= 331 cm + 2 x D + A
Example:
Wall thickness D = 45 cm
Hole diameter 150 cm thus A = 115 cm
L
total
= 331 cm + 2 x 45 cm + 115 cm = 536 cm