TEFLON is trademark of DuPont Corporation.

Frequent visual inspections are recom-

mended to be initially performed for 

nozzles installed in potentially corro-

sive atmospheres to verify the integ-

rity of the materials of construction 

and finish as they may be affected by 

the corrosive conditions present for a 

given installation. Thereafter, annual 

inspections per applicable standards 

are required, in addition to inspec-

tions required by the authority having 

jurisdiction.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of any other authorities having juris-

diction. Contact the installing contrac-

tor or product manufacturer with any 

questions.
Water mist systems should be in-

spected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and part number 

(P/N).

Type ULF AM30 AQUAMIST Nozzles

Specify: Type ULF AM30 AQUA-

MIST Nozzle with Natural Brass finish, 

(specify) temperature rating, P/N 

(specify):

57

°

C (135

°

F) . . . . . . . . . . . . . . . . . . 49-230-1-135 

68

°

C (155

°

F) . . . . . . . . . . . . . . . . . . 49-230-1-155 

79

°

C (175

°

F) . . . . . . . . . . . . . . . . . . 49-230-1-175 

93

°

C (200

°

F). . . . . . . . . . . . . . . . . . 49-230-1-200 

141

°

C (286

°

F) . . . . . . . . . . . . . . . . . 49-230-1-286 

182

°

C (360

°

F). . . . . . . . . . . . . . . . .49-230-1-360

Wrench

Specify: W-Type 6 Sprinkler Wrench, 

P/N 56-000-6-387

Care and 

Maintenance

TYCO Ultra Low Flow AQUAMIST 

Nozzles Type ULF AM30 must be main-

tained and serviced in accordance with 

this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Nozzles which are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic nozzles must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified nozzles must be replaced. 

Nozzles that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the nozzle with a cloth or by 

brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the nozzles before, during, 

and after installation. Nozzles damaged 

by dropping, striking, wrench twist/

slippage, or the like, must be replaced. 

Also, replace any nozzle that has a 

cracked bulb or that has lost liquid from 

its bulb (Ref. Installation section).

Installation

TYCO Ultra Low Flow AQUAMIST 

Nozzles Type ULF AM30 must be 

installed in accordance with this 

section.
Do not install any bulb type nozzle if 

the bulb is cracked or there is a loss 

of liquid from the bulb. With the nozzle 

held horizontally, a small air bubble 

should be present. The diameter of 

the air bubble is approximately 1,6 mm 

(1/16 in.) for the 57

°

C (135

°

F) to 2,4 mm 

(3/32 in.) for the 182

°

C (360

°

F) temper-

ature ratings.
A leak-tight 1/2 inch NPT nozzle joint 

should be obtained by applying a min-

imum-to-maximum torque of 9,5 to 

19,0 Nm (7 to 14 lbs.-ft.). Higher levels 

of torque can distort the nozzle inlet 

and cause leakage or impairment of 

the nozzle.

Type ULF AM30

The Type ULF AM30 AQUAMIST 

Nozzles must be installed in accor-

dance with the following instructions:
Step 1. Install the Type ULF AM30 in the 

upright position as shown in Figure 1.
Step 2. With pipe thread sealant 

ap plied to the pipe threads, hand-

tighten the nozzle into the nozzle fitting.
Step 3. Tighten the nozzle into the 

nozzle fitting using only the W-Type 6 

Wrench (Ref. to Figure 2). With refer-

ence to Figure 1, apply the W-Type 6 

Wrench to the wrench flats.

WRENCH RECESS

(USE ONLY

END "A")

Components:

Strainer

Sealing

Assembly

Frame
Button

Loading

Screw

Bulb

Ejection

Spring

Diffuser

Orifice Insert

6 -

8

-

9

-

-

7

-

1

-

4

-

5

-

-

3

2

5

8

9

7

6

2

4

3

1

1/2" NPT 

DIFFUSER

SHAPE

1-11/16"

(42,9 mm)

WRENCH

FLATS

1.22"

(31,0 mm)

11/16"

(17,5 mm)

2-3/8"

(60,3 mm)

11/16"

(17,5 mm)

7/16" (11,1 mm)

NOMINAL

MAKE-IN

FIGURE 2 

W-TYPE 6 WRENCH

FIGURE 1 

TYPE ULF AM30 AQUAMIST NOZZLE 

NOMINAL DIMENSIONS