Tyco TY1334 Manual Download Page 5

TFP410

Page 5 of 10 

Maximum   

Coverage Area 

(a)

Width x Length 

(b)

 

Ft. x Ft. (m x m)

Maximum 

Spacing

Ft. (m)

DRY PIPE SYSTEM  

Minimum Flow 

(c) 

and Residual Pressure 

Top-of-Deflector-to-Ceiling:   

4 to 6 Inches (100 to 150 mm)

Top-of-Deflector-to-Ceiling:   

6 to 12 Inches (100 to 150 mm)

155°F (68°C)

175°F (79°C) 

155°F (68°C)

175°F (79°C) 

12 x 12

(3,7 x 3,7)

12

(3,7)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

13 GPM (49,2 LPM)

9.6 psi (0,48 bar)

13 GPM (49,2 LPM)

9.6 psi (0,48 bar)

14 x 14

(4,3 x 4,3)

14

(4,3)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

16 x 16

(4,9 x 4,9)

16

(4,9)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

16 x 18

(4,9 x 5,5)

16

(4,9)

19 GPM (71,9 LPM)  

20.5 psi (1,41 bar)  

Not  Applicable

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

16 x 20

(4,9 x 6,1)

16

(4,9)

23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

Not  Applicable

Not  Applicable

Not  Applicable

Sidewall sprinklers, where installed under a ceiling with a slope greater than a 0-inch rise for a 12-inch run to a slope up to a 2-inch  

rise for a 12-inch run, must be located per one of the following:

•  At the high positioned to discharge down the slope.

•  Along the slope and positioned to discharge across the slope.

(a).  For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage      

area for which hydraulic design criteria are stated.

(b).  The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler). 

(c).  The Minimum Flow Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures  

 

are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details. 

TABLE B   

SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)   

FOR HORIZONTAL CEILINGS 

NFPA 13D HYDRAULIC DESIGN CRITERIA

DRY PIPE SYSTEMS 

(Maximum 2-Inch Rise for 12-Inch Run)

ELEVATION

Summary of Contents for TY1334

Page 1: ...filled pipe in addition to not having to increase the number of design sprinklers hydraulic design area for systems designed to NFPA 13 13D or 13R Non water filled pipe will permit options for areas sensitive to freezing The Series LFII Residential Sprinklers has a 4 2 60 5 K Factor that provides the required residential flow rates at reduced pressures enabling smaller pipe sizes and water supply ...

Page 2: ...ating Bulb Deflector 1 Components 2 Button Assembly Frame TOP 57 2 mm 2 1 4 41 3 mm 1 5 8 6 4 5 3 2 1 2 7 8 DIA 73 0 mm RECESSED ESCUTCHEON STYLE 20 FLATS WRENCH CENTERLINE OF WATERWAY 1 2 NPT BOSS END OF DEFLECTOR TOP OF DEFLECTOR 7 16 11 1 mm FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS TY1334 FIGURE 2 STYLE 20 RECESSED ESCUTCHEO...

Page 3: ...sprinkler systems the requirements for Dry System Water Delivery per the Section 8 3 4 3 of the 2010 edition of NFPA 13D apply For a residential hazard in no case shall the time of water delivery exceed 15 seconds for the most remote operating sprinkler Hydraulic Design NFPA 13D and 13R The minimum re quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A B C...

Page 4: ...M 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 19 GPM 71 9 LPM 20 5 psi 1 41 bar 19 GPM 71 9 LPM 20 5 psi 1 41 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 21 GPM 79 5 LPM 25 0 psi 1 72 bar 16 x 20 4 9 x 6 1 16 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar 23 GPM 87 1 LPM 30 0 psi 2 07 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar 26 GPM 98 4 LPM 38 3 psi 2 64 bar Sidewall sprinklers where installed under a ceiling with a...

Page 5: ... 4 9 23 GPM 87 1 LPM 30 0 psi 2 07 bar Not Applicable Not Applicable Not Applicable Sidewall sprinklers where installed under a ceiling with a slope greater than a 0 inch rise for a 12 inch run to a slope up to a 2 inch rise for a 12 inch run must be located per one of the following At the high positioned to discharge down the slope Along the slope and positioned to discharge across the slope a Fo...

Page 6: ...7 bar I 14 GPM 53 0 LPM 11 1 psi 0 77 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar I 17 GPM 64 3 LPM 16 4 psi 1 13 bar 16 x 16 4 9 x 4 9 16 4 9 I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 16 GPM 60 6 LPM 14 5 psi 1 00 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar I 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 19 GPM 71 9 LPM 20 5 psi 1 41 bar I 21 GPM 79 5 LPM 25...

Page 7: ...LPM 18 4 psi 1 27 bar 14 x 14 4 3 x 4 3 14 4 3 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 16 GPM 60 6 LPM 14 5 psi 1 00 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar II 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 18 4 9 x 5 5 16 4 9 II 22 G...

Page 8: ... C 12 x 12 3 7 x 3 7 12 3 7 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 14 x 14 4 3 x 4 3 14 4 3 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 16 4 9 x 4 9 16 4 9 III 16 GPM 60 6 LPM 14 5 psi 1 00 bar III 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 x 18 4 9 x 5 5 16 4 9 N A N A 16 x 20 4 9 x 6 1 16 4 9 N A N A a For coverage area dimensio...

Page 9: ...e Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling Care and Maintenance The RAPID RESPONSE Series LFII Residential Horizontal and Recessed Horizontal Sidewall Sprinklers TY1334 must be maintained and serviced in accordance with the following instructions NOTICE Before closing a fire protection system main control valv...

Page 10: ...ncluding but not limited to labor charges regardless of whether TFSBP was informed about the possi bility of such damages and in no event shall TFSBP s liability exceed an amount equal to the sales price The foregoing warranty is made in lieu of any and all other warranties express or implied including warran ties of merchantability and fitness for a particular purpose This limited warranty sets f...

Reviews: