Installation

The TYCO RIS adapter must be 

installed in accordance with this 

section. Read the General Instructions 

section before preceding to the rele-

vant installation instructions.
Sample RIS adapter installations are 

shown in Figures 3 and 4.

General Instructions

Observe the following guidelines while 

installing the fitting:
•  The 

TYCO  Model TF-3 and TF-4 

Rapid Install Sprinkler (RIS) Adapter 

1 Inch Male Tapered to Female RIS 

Threaded Fitting is compatible with 

only two sprinkler models, TYCO 

Models ESFR-22  and ESFR-25 

RISs.

•  For information about installing 

the TYCO Models ESFR-22 and 

ESFR-25 RISs, refer to technical 

data sheets TFP327 and TFP328 

respectively.

Installing the RIS Adapter

Step 1.

 Thread the RIS adapter onto 

the ESFR RIS sprinkler as shown in 

Figure 2 until the flange is fully seated.

Step 2.

 Apply pipe thread sealant to 

the RIS Adapter pipe threads, and hand 

tighten the sprinkler/adapter assembly 

into the pipe fitting.

Step 3.

 Tighten the assembly into the 

fitting using only the W-Type 1 sprinkler 

wrench as shown in Figure 2.

Note:

 Optional: Use 1 in. pipe and fit-

tings for sprinkler location adjustment 

- for example, an armover or a sprinkler 

drop as shown in Figures 3 and 4.

NOTICE

Ensure the sprinkler threads are clean 

and do not apply sealant such as tape 

or paste. Threads with debris or sealant 

could cause damage or impairment.

NOTICE

A leak-tight 1 in. NPT joint should be 

obtained by applying a minimum to 

maximum torque of 20 to 30 lb-ft (26,8 

to 40,2 N·m). Higher levels of torque 

can distort the sprinkler inlet with con-

sequent leakage or impairment of the 

sprinkler.

NOTICE

Use the NPT threads only to align 

the frame arms with the branch line if 

desired. The RIS flange and adapter 

must remain fully seated as shown in 

Figure 2.

SURFACE

SPRINKLER

FLANGE MATING

(48,1 mm)

1.895" DIA.

SURFACE

GASKET

SEALING

RECESS

GASKET

THREADS

1" MALE

TAPERED PIPE

(40,4 mm)

1.59"

THREADS

RIS

FEMALE

MODEL TF-3 OR TF-4

RIS ADAPTER

FITTING

WITH LINK PROTECTOR

ESFR RIS SPRINKLER

WRENCH

W-TYPE 1

WRENCH

RECESS

FULLY SEAT SPRINKLER INTO

ADAPTER BEFORE INSTALLING

INTO BRANCHLINE FITTING

ESFR

ASSEMBLED

SPRINKLER

INTO ADAPTER

"FITTING SIDE"

SPRINKLER

TOWARDS

ADAPTER

PIPE FITTING

STANDARD BRANCHLINE

FIGURE 2 

MODEL TF-3 OR TF-4 

MALE TAPERED TO 

FEMALE RIS THREADED FITTING 

RIS ADAPTER 

ESFR RIS SPRINKLER 

INSTALLATION

FIGURE 1 

MODEL TF-3 AND TF-4 

1 INCH MALE TAPERED TO FEMALE RIS THREADED FITTING 

RAPID INSTALL SPRINKLER ADAPTER 

FEATURES AND DIMENSIONS

Summary of Contents for TF-3

Page 1: ...R RIS sprinkler Two models of the RIS Adapter 1 Inch Male Tapered to Female RIS Threaded Fitting are available Model TF 3 1 in Male NPT to Female RIS Model TF 4 1 in Male ISO to Female RIS NOTICE The TYCO Model TF 3 and TF 4 Rapid Install Sprinkler Adapter 1 Inch Male Tapered to Female RIS Threaded Fitting described herein must be installed and maintained in compliance with this document as well a...

Page 2: ...ustment for example an armover or a sprinkler drop as shown in Figures 3 and 4 NOTICE Ensure the sprinkler threads are clean and do not apply sealant such as tape or paste Threads with debris or sealant could cause damage or impairment NOTICE A leak tight 1 in NPT joint should be obtained by applying a minimum to maximum torque of 20 to 30 lb ft 26 8 to 40 2 N m Higher levels of torque can distort...

Page 3: ...uthori ties and advise those responsible for monitoring proprietary and or central station alarms Limited Warranty For warranty terms and conditions visit www tyco fire com Ordering Procedure Contact your local distributor for avail ability When placing an order indicate the full product name and Part Number P N RIS Adapter Specify Model specify Rapid Install Sprinkler Adapter 1 inch Male Tapered ...

Page 4: ...ademarks of National Fire Protection Association 1467 Elmwood Avenue Cranston RI 02910 Telephone 1 401 781 8220 2022 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Reviews: